Home Frequency amelioration of an interconnected microgrid system
Article Open Access

Frequency amelioration of an interconnected microgrid system

  • Debayani Mishra EMAIL logo , Manoj Kumar Maharana and Anurekha Nayak
Published/Copyright: May 17, 2022
Become an author with De Gruyter Brill

Abstract

This article validates the operational effectiveness of a fuzzy-based multistage cascaded proportional integral derivative fractional filter (PIDFN) controller which enhances the frequency regulation of an interconnected islanded microgrid system. The effect of the ambiguous nature of renewable energy resources and test cases concerning different load variations are applied to verify the robustness of the proposed controller. The superiority of the proposed controller upon proportional-integral-derivative (PID), fractional-order PID (FOPID), and Fuzzy FOPID controller in minimizing frequency alteration has been verified through MATLAB/SIMULINK environment.

1 Introduction

In the modern era of power system, renewable energy source (RES) efficiently replaces a greater amount of conventional power generation in terms of energy requirement. These sources are amply available, economical, situated at the vicinity of the load, and curtails the transmission and distribution losses in the system. The renewable source with the ability to function at low as well as medium voltage levels that can be operated in integration with the distributed generation sources, controllable units, loads along with the energy storage systems embodying in a small network is designated as a microgrid (MG). Resilience, power system reliability, decrement in the feeder capacity, power quality improvement, and transmission loss reduction are the essential advantages of a microgrid system. The system may operate in grid-connected mode or an islanded mode and maybe a combination of both.

RESs such as solar and wind play an integral source for generating power in a microgrid system. Aberrant wind speed and fluctuation in the intensity of the sun radiation bring disturbance to the efficient operation of the MG. These sources being sporadic in nature results in a discrepancy between the power generation and load demand in the microgrid system. As a consequence, this imbalance affects the deviation of system frequency. So, to maintain the system frequency within its pre-scheduled values, a load frequency control scheme is included in the microgrid system.

Multitude control techniques are available in the literature to control the frequency in a MG system [1,2]. Mohanty et al. have implemented integral (I), proportional-integral (PI), and proportional-integral-derivative (PID) controllers for enhancement of the frequency profile implementing an HVDC link in the system [3]. Owing to the incompetency of the conventional controllers, various advanced controllers are incorporated in the literature. Bevrani et al. have implemented an H-∞ and µ-synthesis controller for minimizing the deviation in frequency in an islanded MG [4]. With the operational advantages, various configurations of fractional-order PID controller are implemented to mitigate the frequency deviation in a multi-area power system [5,6,7,8]. Moreover, the system performance can be improved with fuzzy logic-based fractional-order PID controller [9,10,11,12,13]. Ahmadi et al. have proposed a fuzzy-based PID controller for frequency regulation and control in a multi-source power system [14]. A cascaded scheme of fuzzy-based PID controllers can enhance the system performance for a hybrid power system [15,16]. So, contemplating all the above spheres of research of load frequency control (LFC) in an interconnected MG, a new fuzzy multistage cascade PIDFN controller is considered

Thus, the contributions made by this article are

  1. An interconnected islanded MG system is incorporated comprising photovoltaic (PV), wind, diesel engine generator (DEG), and ultracapacitor.

  2. A fuzzy multistage cascade PIDFN-based controller is included in the system to improve the system’s frequency control.

  3. To evidence the superior operative performance of the proposed controller upon PI, FOPID, and fuzzy FOPID, the dynamic performance of LFC has been explored through MATLAB/Simulink environment contemplating various loading conditions and irregularities in wind and PV power generation.

The arrangement of the article is as follows: Section 2 describes the structure of the proposed MG system and the function of the various components. The control techniques implemented in the system are described in Section 3. Section 4 describes the supremacy of the proposed fuzzy multistage cascade PIDFN controller over other controllers. The robustness of the proposed controller in improving the frequency control is described in concluding Section 5.

2 Description of MG system

The structural representation of an interconnected islanded MG system is depicted in Figure 1. Area 1 is exemplified by DEG, PV, ultracapacitor (ULC), and load whereas area 2 represents wind turbine generator (WTG), ULC, and DEG. A controller is designed to minimize the frequency deviation and attain a steady state when the system is subjected to various disturbances.

Figure 1 
               Proposed microgrid model.
Figure 1

Proposed microgrid model.

Whenever the non-conventional sources break down to supply the desired power to the load, then the DEG acts as a substitute. Ultracapacitor acts as a backup and improves the system stability. The generated load balance is achieved by the DEG and fuel cell (FC). In each MG system, the controller output is connected to the DEG, ULC, and storage unit to diminish the frequency deviation. The elements of the islanded MG system are represented in Table 1. The models of the various components of the hybrid MG system are illustrated in the following sub-sections.

Table 1

System model transfer function and parameter

Model Transfer function Parameters
Diesel engine generator K DG/(STDG + 1) K DG = 0.03 and T DG = 2
Wind turbine K WTG/(STWTG + 1) K WTG = 1 and T WTG = 1.5
PV K PV/STPV + 1 K PV = 1 and T PV = 0.03
Ultracapacitor 1/(STULC + 1) T ULC = 0.08
Synchronizing coefficient K 12/s K 12 = 0.56

2.1 DEG

Variation in solar intensity and wind speed results in the alteration of generated power. DEGs functions as a backup in isolated MG as they hold the capacity to run with higher efficiency, minimal maintenance, and fast speed. Adding to this, it has the ability to atone the power supply to the load due to the alteration of RESs in the MG. The transfer function model representation of DEG is described in Figure 2.

Figure 2 
                  Transfer function model of DEG.
Figure 2

Transfer function model of DEG.

2.2 PV system

A PV system is an aggregation of various PV modules connected in series or parallel. The solar radiation and temperature being erratic in nature produces volatile power from the PV system. The extracted power from the PV cell is calculated as

(1) P PV = η S ϕ ( 1 0.005 ( T a + 25 ) ) ,

where η = PV array efficiency, S = area of the photovoltaic array, ɸ = solar radiation intensity, and T a = surrounding temperature.

The transfer function of the PV system is represented as

(2) TF PV = K PV 1 + s T PV ,

where K PV = Gain of PV array and T PV = time constant of PV array.

2.3 WTG system

The electrical energy produced in the WTG depends on the kinetic energy extracted from the wind. The generated power from the wind turbine system is expressed as,

(3) P WTG = 1 2 ρ A C p ( λ , β ) V w 3 ,

where ρ = density of air (kg/m3), λ = turbine tip speed ratio, V w = wind velocity (m/s), C p = power coefficient, A = area swept by the turbine blade (in m2), and B = pitch angle of the turbine blade.

2.4 ULC

It is a component that has the ability to store charge electrostatically. It can combat thousands of cycles as compared to batteries. The storage unit has faster charge and discharge characteristics. It has negligible resistance and has faster response to power disturbance in the system. The transfer function is expressed as

(4) TF ULC = 1 1 + s T ULC .

2.5 MG system

The power needed to supply the load is supplied from all the sources and the corresponding relationship between alteration in frequency with corresponding power demand is expressed in equation (5) as

(5) Δ f Δ P = K PS 1 + s T PS ,

3 Controller design

Discrepancy in the nature of the wind and sun radiation leads to power disturbance which further distorts the system frequency, so a controller is designed to curtail the frequency deviation. In this article a fuzzy multistage cascade PIDFN controller is proposed which improves the system performance in an interconnected islanded MG system. The controller performance is further compared with other conventional controllers under various conditions.

3.1 PI controller

This controller is an amalgamation of proportional and integral controller, and has a faster response. The PI controller minimizes the divergence in frequency and attains a stable response. The simplified diagram is represented in Figure 3.

Figure 3 
                  PI controller.
Figure 3

PI controller.

3.2 Fractional-order PID controller (FOPID)

FOPID is a distinct PID controller where the derivative and integral orders are fractional and the parameters λ and µ represent integrator and derivative order, respectively. The controller possesses a better performance and is represented as

(6) C ( s ) = K p 1 + K i s λ + K d s μ ,

where K p = proportional gain, K i = integral gain, and K d = derivative gain.

3.3 Fuzzy FOPID

Fuzzy-tuned FOPID controller is an extension of conventional FOPID controller. In this scheme, the parameters of the FOPID controller are altered by using fuzzy inference system. There are two fuzzy inputs i.e., frequency deviation (Δf) and variation in load (ΔP) which update the scaling factors of the proportional gain (K p), integral gain (K I), and derivative gain (K D) [14]. The final values of the FOPID controller are computed as

(7) K P = K P + Δ K ,

(8) K I = K I + Δ K I ,

(9) K D = K D + Δ K .

In the above equations, the FOPID controller’s initial gain value is represented by K P, K I, and K D and the scaling factor calculated from the fuzzy logic controller (FLC) are ΔK P, ΔK I, and ΔK D. The fuzzy inference system (FIS) has six membership functions for change in frequency and three membership functions for change in load. The fuzzy logic controller rules are represented in Table 2.

Table 2

Rules of fuzzy logic controller

ΔfP LON BGN MDN LOP BGP MDP
LO LON BGN MDN LOP MDP LOP
BG BGN BGN BGN MDP MDP MDP
MD MDN BGN BGN LOP MDP MDP

Change in frequency has six membership functions such as low negative (LON), big negative (BGN), medium negative (MDN), low positive (LOP), big positive (BGP), and medium positive (MDP). For alteration in load, there are three membership functions such as low (LO), big (BG), and medium (MD).

3.4 Proposed fuzzy multistage cascade PIDFN controller

In the proposed work, an efficient controller which is a combination of PIDFN-FOPIDFN is connected in series as shown in Figure 4. The controller parameters are tuned by fuzzy inference system for an interconnected MG. The FIS has the same rules as in Table 2. The output of the FIS is given as input to the cascaded controller and its performance is studied in Section 4. The gain values of the PID, FOPID, and filter constant (FN) are selected. Fuzzy logic is used to reduce the deviation in frequency by tuning the parameters of the PIDFN controller (Figure 4).

Figure 4 
                  Schematic representation of the proposed controller.
Figure 4

Schematic representation of the proposed controller.

4 Results and discussion

Faster response and dynamic stability are the required features of a control system. The effectualness of the proposed controller is examined on an interconnected MG system under different operating conditions. The MG system is simulated in MATLAB software. The proposed multistage controller is analyzed on an isolated and multi-area MG system. The predominance of the suggested controller under different scenarios is studied and comparative analysis with other controllers in existing literature is studied.

4.1 Scenario 1 – Individual MG-step load

A single MG system comprising of PV, WTG, DEG, FC, and ULC is subjected to a step load increment of 0.01 p.u at time t = 20 s. A relative comparison of the dynamic responses in frequency with PI, FOPID, and fuzzy FOPID are shown in Figure 5, respectively.

Figure 5 
                  Frequency deviation during step load.
Figure 5

Frequency deviation during step load.

It is depicted from Figure 5 that with PI, FOPID, and fuzzy FOPID, the frequency deviation could be reduced with the settling times of 32, 24, and 20 s, respectively. However, with the proposed fuzzy multistage cascade PIDFN controller, the frequency deviation is effectively improved and system attained steady state in 21 s. The comparative analysis of the dynamic response in terms of undershoot, overshoot, and settling time is given in Table 3.

Table 3

Comparative analysis of system response for scenario 1

Parameters Controllers
PI FOPID Fuzzy FOPID Proposed controller
Settling time 32 30 24 21
Peak overshoot 0.23 0.15 0.12 0.03
Peak undershoot −0.22 −0.08 −0.03 −0.01

The comparison of undershoots, overshoots, and settling times with PI, FOPID, fuzzy FOPID and proposed multistage cascade PIDFN controllers presented in the Table 3 clearly evidenced the robustness of the proposed controller.

4.2 Scenario 2 – Individual MG-multiple load disturbance

The MG system is administered to a multiple load disturbance which encompasses a 3% step load increase at t = 10 s and 1% step load decrease at t = 20 s. A comparative performance of the dynamic performance of frequency is represented in Figure 6.

Figure 6 
                  Frequency deviation during multiple load disturbance.
Figure 6

Frequency deviation during multiple load disturbance.

It can be noticed that the system’s response with PI, FOPID, and fuzzy FOPID controller became more oscillatory and required a larger settling time. However, with the proposed fuzzy multistage cascade PIDFN controller, the damped oscillations are significantly alleviated and the system attains stability faster than the other three controllers. The comparative analysis of the dynamic response in terms of undershoot, overshoot, and settling time is given in Table 4.

Table 4

Comparative analysis of system response for scenario 2

Parameters Controllers
PI FOPID Fuzzy FOPID Proposed controller
Settling time 25 24 22 20
Peak overshoot 0.2
Peak undershoot −0.21 −0.27 −0.3 −0.05

Table 4 verified the role of the proposed controller in lessening the settling time and adding to system stability faster than other suggested controllers even with a multi-step load perturbation.

4.3 Scenario 3 – Interconnected MG-step load disturbance

In this system the MG-1 comprises of PV, DEG, FC, and ULC and MG-2 consists of WTG, DEG, FC, and ULC. The two MG system is connected to a tie-line and MG-1 is subjected to a 1% step load increase at t = 20 s. A relative comparison of the dynamic responses established for differences in frequency ΔF 1 and ΔF 2 and change in exchange power through tie line ΔP TIE with PI, FOPID, fuzzy FOPID, and fuzzy multistage cascade PIDFN controller are shown in Figure 7(a)–(c), respectively.

Figure 7 
                  Frequency deviation in multi-microgrid for step load disturbance. (a) Frequency deviation in area 1; (b) frequency deviation in area 2; (c) frequency deviation in tie line.
Figure 7

Frequency deviation in multi-microgrid for step load disturbance. (a) Frequency deviation in area 1; (b) frequency deviation in area 2; (c) frequency deviation in tie line.

It is depicted from Figure 7(a) that with PI, FOPID, and fuzzy-tuned FOPID controllers, the frequency deviation of area-1 could be reduced with the settling times of 25, 24, and 23 s, respectively. However, with the proposed fuzzy multistage cascade PIDFN controller, the deviation in area-1 frequency is effectively improved and the system attained steady state in 21 s.

In Figure 7(b), the frequency of area-2 with a PI, FOPID, and fuzzy FOPID controller results in an oscillatory response, while with the proposed controller, the frequency response at area-2 is improved and reached steady state in 14 s.

From Figure 7(c) it is observed that with PI, FOPID, and fuzzy FOPID controllers, the tie line power flow between the control areas have declined and also failed to attain their prescheduled value. The proposed controller is robust enough to bring down the tie line power deviation with a settling time of 21 s. The comparative analysis of the dynamic response in terms of undershoot, overshoot, and settling time is given in Table 5.

Table 5

Comparative analysis of system response for scenario 3

Parameters Controllers
PI FOPID Fuzzy FOPID Prop. controller
Area 1 Settling time 25 24 23 21
Peak overshoot 0.03 0.08 0.12 0.02
Peak undershoot −0.02 −0.015 −0.01
Area 2 Settling time 33 30 22 14
Peak overshoot 0.041 0.043 0.005
Peak undershoot −0.026 −0.0012
Tie line Settling Time 28 24 23 21
Peak overshoot 0.04 0.07 0.08 0.02
Peak undershoot −0.01 −0.06 −0.12 −0.005

The divergence of peak undershoots, overshoots, and settling times with PI, FOPID, fuzzy FOPID, and proposed fuzzy cascade PIDFN controllers presented in the Table 5 clearly evidenced the robustness of the suggested controller.

4.4 Scenario 4 – Interconnected MG-multiple load disturbance

In this case, MG-1 is subjected to a variable step load perturbation at t = 20 s. The frequency response of various controllers is represented in Figure 8(a)–(c), respectively.

Figure 8 
                  Frequency deviation in multi-microgrid for multiple load disturbance. (a) Frequency deviation in area 1; (b) frequency deviation in area 2; (c) frequency deviation in tie line.
Figure 8

Frequency deviation in multi-microgrid for multiple load disturbance. (a) Frequency deviation in area 1; (b) frequency deviation in area 2; (c) frequency deviation in tie line.

From Figure 8(a)–(c), it is observed that although the investigated system is put through a multistep load variation, the proposed controller is able to operate persistently with sustained oscillations. The values of undershoots, overshoots, and settling times of the system responses are tabulated in Table 6.

Table 6

Comparative analysis of system response for scenario 4

Parameters Controllers
PI FOPID Fuzzy FOPID Prop. controller
Area 1 Settling time 28 23 20 18
Peak overshoot 0.32
Peak undershoot −0.18 −0.24 −0.26 −0.02
Area 2 Settling time 35 25 14 12
Peak overshoot 0.06
Peak undershoot −0.01 −0.07 −0.1 −0.005
Tie line Settling time 27 24 22 20
Peak overshoot −0.15 0.23 0.002
Peak undershoot −0.13 −0.23 −0.21 −0.01

Table 6 verified the role of the proposed controller in lessening the settling time and adding to system stability faster than the other suggested controllers in area 1, area 2, and tie line even with a multi-step load perturbations.

4.5 Scenario 5 – Interconnected MG-constant RES in MG-1

In this scenario, the wind power generation is assumed to be constant in MG-1. Step load disturbance occurs in MG-1 due to variation in the nature of solar intensity frequency deviation in the system. The suggested controller is predominant over other controllers and has better response as shown in Figure 9(a)–(c).

Figure 9 
                  Frequency deviation in multi-microgrid for constant RES in area 1. (a) Frequency Ddeviation in area 1; (b) frequency deviation in area 2; (c) frequency deviation in tie line.
Figure 9

Frequency deviation in multi-microgrid for constant RES in area 1. (a) Frequency Ddeviation in area 1; (b) frequency deviation in area 2; (c) frequency deviation in tie line.

It is illustrated from Figure 9(a)–(c) that the frequency deviation in area 1 and area 2 are reduced with step load variation in the MG system. The values of undershoots, overshoots, and settling times of the system responses are tabulated in Table 7.

Table 7

Comparative analysis of system response for scenario 5

Parameters Controllers
PI FOPID Fuzzy FOPID Prop. controller
Area 1 Settling time 18 12 10 8
Peak overshoot 0.05 0.1 0.12 0.02
Peak undershoot −0.01
Area 2 Settling time 15 14 12 10
Peak overshoot 0.07 0.045 0.025 0.01
Peak undershoot −0.002
Tie line Settling time 14 23 8 6
Peak overshoot 0.04 0.08 0.09 0.02
Peak undershoot −0.02 −0.05 −0.06

From Table 7 it is evident that with the test scenario 5 established for constant wind speed in area 1, the proposed controller can function reliably adding to system stability.

4.6 Scenario 6 – Interconnected MG- constant RES in MG-2

In this case, the MG-2 system has constant solar intensity and MG-1 system has fluctuating wind power generation. To verify the supremacy of the proposed controller, the frequency response is depicted in Figure 10(a)–(c).

Figure 10 
                  Frequency deviation in multi-microgrid for constant RES in area 2.  (a) Frequency deviation in area 1; (b) frequency deviation in area 2; (c) frequency deviation in tie line.
Figure 10

Frequency deviation in multi-microgrid for constant RES in area 2. (a) Frequency deviation in area 1; (b) frequency deviation in area 2; (c) frequency deviation in tie line.

From Figure 10(a)–(c), it is observed that although the investigated system is put through variation in wind speed in area 2, the proposed controller is able to operate persistently with sustained oscillations. The values of undershoots, overshoots, and settling times of the system responses are tabulated in Table 8.

Table 8

Comparative analysis of system response for scenario 6

Parameters Controllers
PI FOPID Fuzzy FOPID Prop. controller
Area 1 Settling time 26 25 23 20
Peak overshoot 0.08 0.12 0.1 0.02
Peak undershoot −0.04 −0.02 −0.01
Area 2 Settling time 29 27 25 15
Peak overshoot 0.06 0.07 0.05 0.001
Peak undershoot −0.04 −0.03 −0.02
Tie line Settling time 27 25 23 20
Peak overshoot 0.04 0.08 0.07 0.01
Peak undershoot −0.06 −0.05 −0.01 −0.001

Table 8 verified the role of the proposed controller in lessening the settling time and adding to system stability faster than other suggested controllers even with a perturbation in wind power.

5 Conclusion

A fuzzy-based multistage cascaded PIDFN controller has been proposed in this article to reduce the system’s frequency deviation when the interconnected isolated MG is encountered with distinct load variations. In addition to this, alteration in solar radiation and fluctuation in wind speed have been considered to get a deep insight into the LFC analysis. The efficacy of the proposed controller in enhancing dynamic responses in terms of overshoot, undershoot, and settling time has been compared with PI, FOPID, and Fuzzy-based FOPID controllers. The proposed fuzzy-based multistage cascaded PIDFN controller is robust enough in minimizing frequency deviation at area-1 to settle at 21 s, in area-2 at 14 s, and tie-line power response at 20 s, only when subjected to step load perturbation. The detailed analysis of the dynamic performance of the proposed controller is represented in Tables 3–8, respectively. The comparative analysis of the simulation results for different test scenarios with the proposed controller confirmed its robustness of it.

  1. Conflict of interest: Authors state no conflict of interest.

  2. Data availability statement: All data generated or analyzed during this study are included in this research article.

References

[1] Kantamneni A, Brown LE, Parker G, Weaver WW. Survey of multi-agent systems for microgrid control. Eng Appl Artif Intell. 2015 Oct 1;45:192–203.10.1016/j.engappai.2015.07.005Search in Google Scholar

[2] Annamraju A, Nandiraju S. A novel fuzzy tuned multistage PID approach for frequency dynamics control in an islanded microgrid. Int Trans Electr Energy Syst. 2020 Dec;30(12):e12674.10.1002/2050-7038.12674Search in Google Scholar

[3] Yammani C, Maheswarapu S. Load frequency control of multi-microgrid system considering renewable energy sources using grey wolf optimization. Smart Sci. 2019 Jul;7(3):198–217.10.1080/23080477.2019.1630057Search in Google Scholar

[4] Bevrani H, Feizi MR, Ataee S. Robust frequency control in an islanded microgrid: H∞ and μ-synthesis approaches. Int J Electr Power & Energy Syst. 2012 Dec 1;43(1):262–79.10.1109/TSG.2015.2446984Search in Google Scholar

[5] Latha R, Palanivel S, Kanakaraj J. Frequency control of microgrid based on compressed air energy storage system. Distrib Gener & Alternative Energy J. 2012 Sep 1;27(4):8–19.10.1080/21563306.2012.10554219Search in Google Scholar

[6] Majumder R, Chaudhuri B, Ghosh A, Majumder R, Ledwich G, Zare F. Improvement of stability and load sharing in an autonomous microgrid using supplementary droop control loop. IEEE Trans Power Syst. 2009 Oct 30;25(2):796–808.10.1109/PES.2010.5589665Search in Google Scholar

[7] Marwali MN, Jung JW, Keyhani A. Stability analysis of load sharing control for distributed generation systems. IEEE Trans Energy Convers. 2007 Aug 20;22(3):737–45.10.1109/TEC.2006.881397Search in Google Scholar

[8] Serban I, Marinescu C. Control strategy of three-phase battery energy storage systems for frequency support in microgrids and with uninterrupted supply of local loads. IEEE Trans power Electron. 2013 Sep 24;29(9):5010–20.10.1109/TPEL.2013.2283298Search in Google Scholar

[9] Guha D, Roy PK, Banerjee S. Grey Wolf optimization to solve load frequency control of an interconnected power system: GWO used to solve LFC problem. Int J Energy Optim Eng (IJEOE). 2016 Oct 1;5(4):62–83.10.4018/IJEOE.2016100104Search in Google Scholar

[10] Jayachandran M, Ravi G. Decentralized model predictive hierarchical control strategy for islanded AC microgrids. Electr Power Syst Res. 2019 May 1;170:92–100.10.1016/j.epsr.2019.01.010Search in Google Scholar

[11] Kumar B, Adhikari S, Datta S, Sinha N. Real time simulation for load frequency control of multisource microgrid system using grey wolf optimization based modified bias coefficient diagram method (GWO-MBCDM) controller. J Electr Eng & Technol. 2021 Jan;16(1):205–21.10.1007/s42835-020-00596-2Search in Google Scholar

[12] Sanki P, Mazumder S, Basu M, Pal PS, Das D. Moth flame optimization based fuzzy-PID controller for power–frequency balance of an islanded microgrid. J Inst Eng (India): Ser B. 2021 Oct;102(5):997–1006.10.1007/s40031-021-00607-4Search in Google Scholar

[13] Shokoohi S, Golshannavaz S, Khezri R, Bevrani H. Intelligent secondary control in smart microgrids: an on-line approach for islanded operations. Optim Eng. 2018 Dec;19(4):917–36.10.1007/s11081-018-9382-9Search in Google Scholar

[14] Ahmadi S, Talami SH, Sahnesaraie MA, Dini F, Tahernejadjozam B, Ashgevari Y. FUZZY aided PID controller is optimized by GA algorithm for load frequency control of multi-source power systems. In 2020 IEEE 18th World Symposium on Applied Machine Intelligence and Informatics (SAMI). IEEE; 2020 Jan 23. pp. 000207-000212.10.1109/SAMI48414.2020.9108759Search in Google Scholar

[15] Mishra D, Nayak A, Maharana MK. Frequency alleviation in an AC Microgrid using Fuzzy-PI controller. 2021 1st International Conference on Power Electronics and Energy (ICPEE). IEEE; 2021 Jan 2. p. 1–4.10.1109/ICPEE50452.2021.9358738Search in Google Scholar

[16] Sahu PC, Mohapatra S, Sahoo S, Sahu BK, Debnath MK. 2021 International Conference in Advances in Power, Signal, and Information Technology (APSIT) 2021 Oct 8. IEEE; p. 1–5.Search in Google Scholar

Received: 2021-07-10
Revised: 2021-12-23
Accepted: 2022-04-26
Published Online: 2022-05-17

© 2022 Debayani Mishra et al., published by De Gruyter

This work is licensed under the Creative Commons Attribution 4.0 International License.

Articles in the same Issue

  1. Regular Articles
  2. Performance of a horizontal well in a bounded anisotropic reservoir: Part I: Mathematical analysis
  3. Key competences for Transport 4.0 – Educators’ and Practitioners’ opinions
  4. COVID-19 lockdown impact on CERN seismic station ambient noise levels
  5. Constraint evaluation and effects on selected fracture parameters for single-edge notched beam under four-point bending
  6. Minimizing form errors in additive manufacturing with part build orientation: An optimization method for continuous solution spaces
  7. The method of selecting adaptive devices for the needs of drivers with disabilities
  8. Control logic algorithm to create gaps for mixed traffic: A comprehensive evaluation
  9. Numerical prediction of cavitation phenomena on marine vessel: Effect of the water environment profile on the propulsion performance
  10. Boundary element analysis of rotating functionally graded anisotropic fiber-reinforced magneto-thermoelastic composites
  11. Effect of heat-treatment processes and high temperature variation of acid-chloride media on the corrosion resistance of B265 (Ti–6Al–4V) titanium alloy in acid-chloride solution
  12. Influence of selected physical parameters on vibroinsulation of base-exited vibratory conveyors
  13. System and eco-material design based on slow-release ferrate(vi) combined with ultrasound for ballast water treatment
  14. Experimental investigations on transmission of whole body vibration to the wheelchair user's body
  15. Determination of accident scenarios via freely available accident databases
  16. Elastic–plastic analysis of the plane strain under combined thermal and pressure loads with a new technique in the finite element method
  17. Design and development of the application monitoring the use of server resources for server maintenance
  18. The LBC-3 lightweight encryption algorithm
  19. Impact of the COVID-19 pandemic on road traffic accident forecasting in Poland and Slovakia
  20. Development and implementation of disaster recovery plan in stock exchange industry in Indonesia
  21. Pre-determination of prediction of yield-line pattern of slabs using Voronoi diagrams
  22. Urban air mobility and flying cars: Overview, examples, prospects, drawbacks, and solutions
  23. Stadiums based on curvilinear geometry: Approximation of the ellipsoid offset surface
  24. Driftwood blocking sensitivity on sluice gate flow
  25. Solar PV power forecasting at Yarmouk University using machine learning techniques
  26. 3D FE modeling of cable-stayed bridge according to ICE code
  27. Review Articles
  28. Partial discharge calibrator of a cavity inside high-voltage insulator
  29. Health issues using 5G frequencies from an engineering perspective: Current review
  30. Modern structures of military logistic bridges
  31. Retraction
  32. Retraction note: COVID-19 lockdown impact on CERN seismic station ambient noise levels
  33. Special Issue: Trends in Logistics and Production for the 21st Century - Part II
  34. Solving transportation externalities, economic approaches, and their risks
  35. Demand forecast for parking spaces and parking areas in Olomouc
  36. Rescue of persons in traffic accidents on roads
  37. Special Issue: ICRTEEC - 2021 - Part II
  38. Switching transient analysis for low voltage distribution cable
  39. Frequency amelioration of an interconnected microgrid system
  40. Wireless power transfer topology analysis for inkjet-printed coil
  41. Analysis and control strategy of standalone PV system with various reference frames
  42. Special Issue: AESMT
  43. Study of emitted gases from incinerator of Al-Sadr hospital in Najaf city
  44. Experimentally investigating comparison between the behavior of fibrous concrete slabs with steel stiffeners and reinforced concrete slabs under dynamic–static loads
  45. ANN-based model to predict groundwater salinity: A case study of West Najaf–Kerbala region
  46. Future short-term estimation of flowrate of the Euphrates river catchment located in Al-Najaf Governorate, Iraq through using weather data and statistical downscaling model
  47. Utilization of ANN technique to estimate the discharge coefficient for trapezoidal weir-gate
  48. Experimental study to enhance the productivity of single-slope single-basin solar still
  49. An empirical formula development to predict suspended sediment load for Khour Al-Zubair port, South of Iraq
  50. A model for variation with time of flexiblepavement temperature
  51. Analytical and numerical investigation of free vibration for stepped beam with different materials
  52. Identifying the reasons for the prolongation of school construction projects in Najaf
  53. Spatial mixture modeling for analyzing a rainfall pattern: A case study in Ireland
  54. Flow parameters effect on water hammer stability in hydraulic system by using state-space method
  55. Experimental study of the behaviour and failure modes of tapered castellated steel beams
  56. Water hammer phenomenon in pumping stations: A stability investigation based on root locus
  57. Mechanical properties and freeze-thaw resistance of lightweight aggregate concrete using artificial clay aggregate
  58. Compatibility between delay functions and highway capacity manual on Iraqi highways
  59. The effect of expanded polystyrene beads (EPS) on the physical and mechanical properties of aerated concrete
  60. The effect of cutoff angle on the head pressure underneath dams constructed on soils having rectangular void
  61. An experimental study on vibration isolation by open and in-filled trenches
  62. Designing a 3D virtual test platform for evaluating prosthetic knee joint performance during the walking cycle
  63. Special Issue: AESMT-2 - Part I
  64. Optimization process of resistance spot welding for high-strength low-alloy steel using Taguchi method
  65. Cyclic performance of moment connections with reduced beam sections using different cut-flange profiles
  66. Time overruns in the construction projects in Iraq: Case study on investigating and analyzing the root causes
  67. Contribution of lift-to-drag ratio on power coefficient of HAWT blade for different cross-sections
  68. Geotechnical correlations of soil properties in Hilla City – Iraq
  69. Improve the performance of solar thermal collectors by varying the concentration and nanoparticles diameter of silicon dioxide
  70. Enhancement of evaporative cooling system in a green-house by geothermal energy
  71. Destructive and nondestructive tests formulation for concrete containing polyolefin fibers
  72. Quantify distribution of topsoil erodibility factor for watersheds that feed the Al-Shewicha trough – Iraq using GIS
  73. Seamless geospatial data methodology for topographic map: A case study on Baghdad
  74. Mechanical properties investigation of composite FGM fabricated from Al/Zn
  75. Causes of change orders in the cycle of construction project: A case study in Al-Najaf province
  76. Optimum hydraulic investigation of pipe aqueduct by MATLAB software and Newton–Raphson method
  77. Numerical analysis of high-strength reinforcing steel with conventional strength in reinforced concrete beams under monotonic loading
  78. Deriving rainfall intensity–duration–frequency (IDF) curves and testing the best distribution using EasyFit software 5.5 for Kut city, Iraq
  79. Designing of a dual-functional XOR block in QCA technology
  80. Producing low-cost self-consolidation concrete using sustainable material
  81. Performance of the anaerobic baffled reactor for primary treatment of rural domestic wastewater in Iraq
  82. Enhancement isolation antenna to multi-port for wireless communication
  83. A comparative study of different coagulants used in treatment of turbid water
  84. Field tests of grouted ground anchors in the sandy soil of Najaf, Iraq
  85. New methodology to reduce power by using smart street lighting system
  86. Optimization of the synergistic effect of micro silica and fly ash on the behavior of concrete using response surface method
  87. Ergodic capacity of correlated multiple-input–multiple-output channel with impact of transmitter impairments
  88. Numerical studies of the simultaneous development of forced convective laminar flow with heat transfer inside a microtube at a uniform temperature
  89. Enhancement of heat transfer from solar thermal collector using nanofluid
  90. Improvement of permeable asphalt pavement by adding crumb rubber waste
  91. Study the effect of adding zirconia particles to nickel–phosphorus electroless coatings as product innovation on stainless steel substrate
  92. Waste aggregate concrete properties using waste tiles as coarse aggregate and modified with PC superplasticizer
  93. CuO–Cu/water hybrid nonofluid potentials in impingement jet
  94. Satellite vibration effects on communication quality of OISN system
  95. Special Issue: Annual Engineering and Vocational Education Conference - Part III
  96. Mechanical and thermal properties of recycled high-density polyethylene/bamboo with different fiber loadings
  97. Special Issue: Advanced Energy Storage
  98. Cu-foil modification for anode-free lithium-ion battery from electronic cable waste
  99. Review of various sulfide electrolyte types for solid-state lithium-ion batteries
  100. Optimization type of filler on electrochemical and thermal properties of gel polymer electrolytes membranes for safety lithium-ion batteries
  101. Pr-doped BiFeO3 thin films growth on quartz using chemical solution deposition
  102. An environmentally friendly hydrometallurgy process for the recovery and reuse of metals from spent lithium-ion batteries, using organic acid
  103. Production of nickel-rich LiNi0.89Co0.08Al0.03O2 cathode material for high capacity NCA/graphite secondary battery fabrication
  104. Special Issue: Sustainable Materials Production and Processes
  105. Corrosion polarization and passivation behavior of selected stainless steel alloys and Ti6Al4V titanium in elevated temperature acid-chloride electrolytes
  106. Special Issue: Modern Scientific Problems in Civil Engineering - Part II
  107. The modelling of railway subgrade strengthening foundation on weak soils
  108. Special Issue: Automation in Finland 2021 - Part II
  109. Manufacturing operations as services by robots with skills
  110. Foundations and case studies on the scalable intelligence in AIoT domains
  111. Safety risk sources of autonomous mobile machines
  112. Special Issue: 49th KKBN - Part I
  113. Residual magnetic field as a source of information about steel wire rope technical condition
  114. Monitoring the boundary of an adhesive coating to a steel substrate with an ultrasonic Rayleigh wave
  115. Detection of early stage of ductile and fatigue damage presented in Inconel 718 alloy using instrumented indentation technique
  116. Identification and characterization of the grinding burns by eddy current method
  117. Special Issue: ICIMECE 2020 - Part II
  118. Selection of MR damper model suitable for SMC applied to semi-active suspension system by using similarity measures
Downloaded on 8.9.2025 from https://www.degruyterbrill.com/document/doi/10.1515/eng-2022-0038/html
Scroll to top button