Startseite Use of nondestructive test methods to determine the thickness and compressive strength of unilaterally accessible concrete components of building
Artikel Open Access

Use of nondestructive test methods to determine the thickness and compressive strength of unilaterally accessible concrete components of building

  • Tomasz Gorzelańczyk EMAIL logo und Krzysztof Schabowicz
Veröffentlicht/Copyright: 12. Februar 2025
Veröffentlichen auch Sie bei De Gruyter Brill

Abstract

This study presents tests for determining the thickness and compressive strength of unilaterally accessible concrete components of a building, which in this case is a cable-supported building (referred to as Trzonolinowiec) located in Wroclaw, Poland. Nondestructive test methods, the ultrasonic tomography method and the sclerometric method, were used for the tests. The thickness of the unilaterally accessible core of the building was determined using the ultrasonic tomography method. An analysis of the images obtained in this way showed that the thickness of the core’s concrete wall varies along the height of the building. The largest core wall thickness, amounting to 350–400 mm, was detected at a height between the ground floor and the first floor. At a height between the first floor and the second floor, the wall thickness amounts to 280–300 m. For the next floors, wall thickness ranges from 140 to 200 mm. It should be noted that the specified thicknesses of the core wall clearly decrease with the height of the building. On the last floor, the lowest ones were specified, in the range of 140–160 mm. The ultrasonic tomography method was found to be highly useful for determining the thickness of unilaterally accessible concrete members. The sclerometric tests carried out on the concrete walls of the building’s core clearly showed a slight variation in the compressive strength of the concrete. In most of the measuring points, the concrete was found to be a class of C12/15. In a few places the concrete was found to be a class of C16/20. The results of the nondestructive testing were used to build a BIM model of the Trzonolinowiec building and for structural calculations. The test results turned out to be very interesting and of critical importance for the further use of this building. The research conducted by the authors showed that the selected non-destructive methods proved useful for assessing the strength of concrete and the thickness of the concrete wall of the core. Based on the obtained results, it was possible to model the thickness of the core using BIM and then perform structural and strength analyses. The obtained results should be assessed in the category of input data that can be used in later analyses. In this aspect, it can be considered a small contribution to the progress in the use of non-destructive testing in future modeling applications.

1 Introduction

Nondestructive test methods have been commonly used in the building industry for decades. They are used in the broadly understood diagnosis of built structures, being particularly useful in testing structural components made of concrete [1,2,3]. Considering the unique structure of the building investigated as part of this study, especially the fact that its concrete core was only unilaterally accessible and no boreholes could be made in it, the authors concluded that it would be most expedient to use the sclerometric method and the ultrasonic method to determine the thickness and compressive strength of the building’s core. The methods are described further in this article. As the investigated building is rare not only in Poland, but also in the world because of its atypical structure, the authors decided to describe it in more detail.

The Cable-Supported House, informally referred to as “Trzonolinowiec,” is a modernistic building located at 72–74 Tadeusz Kościuszko Street. It was built in the years 1961–1967 [4,5]. A photograph of this building is shown in Figure 1. The Trzonolinowiec has 12 storeys accommodating 44 flats. On the ground floor level there is a service storey, while above the roof level, within the building core outline, a lift machine room is situated. The building was erected according to a design by Andrzej Skorupa and Jacek Burzyński [4,5], which, however, had been considerably modified and impoverished by, among other things, reducing the amount of glazing [4,5]. It is one of the few buildings of this type in Europe. The building was awarded the title of the Wroclaw House of the Year for 1967 [4].

Figure 1 
               View of Trzonolinowiec in Wroclaw (photograph by T. Gorzelańczyk).
Figure 1

View of Trzonolinowiec in Wroclaw (photograph by T. Gorzelańczyk).

The building’s basic structural components are a reinforced concrete core and a system of 12 steel cables. The core is 42.0 m high, and its outer dimensions are 5.10 m × 5.10 m. It was founded on a 1.20 m thick 12.0 m × 12.0 m base slab. The building’s core includes a reinforced concrete lift shaft, a staircase, a rubbish chute shaft, and service shafts (in the N and S walls). The floor slabs of the storey landings are monolithic and made of reinforced concrete and constitute an integral part of the core, also as regards its bracing. The empty spaces between the floor slabs and the ceiling slabs are used as ducts for pumping hot air from the radiant ceiling-floor heating system used.

The steel cables are anchored to the core’s top edge, and their cross section varies from 127 steel strands ϕ5 mm on the topmost storey to 19 steel strands ϕ5 mm on the bottommost storey.

The prefabricated triangular load-bearing floor slabs are 4 cm thick and have the dimensions of 2.4 m × 4.3 m and 2.35 m × 4.2 m. They are strengthened with 19 cm × 4 cm ribs. The slabs were on-site monolithically integrated into four-piece squares and their one edge or corner on the one side was rested on the core, whereas their other corners were suspended using steel cables. Three-centimetre thick ceiling slabs (these slabs are not structural components, carrying only their own weight) with 7 cm × 4 cm ribs were suspended from the floor slabs.

The curtain walls are made of three-layer PW-8 panels, insulated with polyurethane and mounted on the load-bearing steel frame structure. Originally, they were externally clad with flat asbestos cement sheeting. The partitions were made of 12 cm-thick aerated concrete. In the case of the walls between dwelling units, they were made as double with an inner layer with a felt insert.

The building was erected using an innovative method combining monolithic reinforced concrete structures with the slipform technique and the lifting of floor slabs suspended on cables using hydraulic cylinders designed by T. Tenidowski [4]. First, the basement storey was built and a base slab for founding the core (a basic component of the load-carrying system of Trzonolinowiec) was prepared. The core was erected using slipform shuttering. After the core’s load-bearing walls were built within a given storey, the shutters were moved one storey up. Simultaneously, using hydraulic jacks, the erection head was raised, and together with it, the floor slabs (cast in situ on the ground floor level) of the successive storeys were pulled up on 12 steel cables. The latter were passed through holes in the slabs so that each of the cables had its one end under the bottommost slab while its other end was fixed to the head placed on the topmost slab. The successive “layers” of slabs were supported on the successively cast levels of the core. After all the dwelling storeys had been built, the core’s bottommost storey (the ground floor storey) was cast. Once the building had been erected the cables (cable stays) were tightened and anchored in the foundation and in the head. Then, the floor slabs were joined to the core and the cables were protected with an asbestos concrete surround [6]. Archival construction progress photographs showing the stages in the erection of the building are presented in Figure 2. The authors obtained the photographs from the collections of the Museum of Architecture in Wrocław.

Figure 2 
               Archival construction progress photographs showing stages in Trzonolinowiec erection (Collection of the Museum of Architecture in Wroclaw).
Figure 2

Archival construction progress photographs showing stages in Trzonolinowiec erection (Collection of the Museum of Architecture in Wroclaw).

In the years 1975–76, the building underwent a general overhaul whose aim was to brace the structure as the building had been found to vibrate excessively under wind loading. The vertical sections of the load-bearing cables were encased in reinforced concrete columns (25 cm × 25 cm in cross section) in order to rest the slabs on the columns so that they were no longer suspended on the cables. In the ground floor and basement parts, the cables were encased with C240 steel sections.

After several decades of being in service and neglect due to no current and maintenance repairs, the building reached an imminent failure condition, which means that at any moment, a failure of the structural components (a structural collapse) endangering the life and health of the residents can occur [7].

Because of the above, the city authorities and the building manager took action to assess the condition of the building and its repair. For this purpose, a research team made up of scientists from the Civil Engineering Faculty of Wroclaw University of Science and Technology, headed by Prof. Krzysztof Schabowicz, was appointed. The authors carried out a considerable number of tests in the building, including nondestructive tests. One of the elements of the condition survey report being prepared was to make a model of the building using Building Information Modelling (BIM) [8,9]. This model was then to be used to prepare a model for a numerical FEM analysis and structural calculations of selected structural components. In order to make a BIM model information about, among other things, the thickness of the building’s concrete core and its compressive strength was needed. For this purpose, nondestructive test methods, i.e. the sclerometric method and the ultrasonic method, were used. One should note that the building’s core was unilaterally accessible (only from the staircase), which made it difficult to estimate the thickness of the core’s walls. Moreover, no concrete core samples could be taken from it.

The literature shows that non-destructive methods are widely used in the diagnosis of concrete elements, including the localization of various defects (especially cracks) and inclusions [10,11,12]. They can also be used successfully to assess the quality of repairs to concrete elements, as shown, for example, in the work [13]. Non-destructive methods are commonly used in the testing of road infrastructure elements [14] and concrete with various fibres [15]. The NDT methods are highly suitable for estimating the thickness of unilaterally accessible walls [16]. The latest acoustic NDT methods, such as ultrasonic tomography, which is currently increasingly commonly used for testing the condition of structures made of concrete [17,18], including massive members of hydroelectric power plants accessible only unilaterally [19], can be useful for this purpose. The usefulness of the ultrasonic tomography method was proven by Gorzelańczyk et al. [20,21], who successfully determined the thickness of the concrete walls of a heat pipe-carrying tunnel and that of the concrete shell of a mine lift shaft. To determine the compressive strength of concrete in structural components, it is recommended to use the sclerometric method and the ultrasonic method. The methods have been known and successfully used for several decades [1,15]. They are especially recommended in a situation when no core samples can be taken from the structure and tested in a testing machine to determine the compressive strength [22,23]. It should be noted here that further in this article, only tests carried out using the sclerometric method to determine the strength of the concrete are presented. Despite the many attempts made using an ultrasonic concrete tester and the surface transmission method, the strength of the concrete could not be reliably estimated. Due to the unilateral access to the tested concrete members of the building’s core, it was also impossible to conduct tests using the direct transmission method by placing ultrasonic transducers opposite each other on the two sides of the tested member.

At the end of this section, it is worth emphasizing that the authors did not aim to indicate a gap in knowledge because the non-destructive methods used in the work are widely known in the literature. It was important for the authors to demonstrate that the selected methods will be successfully applied to the object in question, especially due to the one-sided access to the tested elements.

2 Description of tests

The nondestructive equipment, an Acoustic Control System Mira A1040 ultrasonic tomograph and a Schmidt hammer type N, shown in Figure 3, was used to test the building’s concrete core.

Figure 3 
               Nondestructive equipment used for testing: (a) ultrasonic tomograph and (b) type N Schmidt hammer.
Figure 3

Nondestructive equipment used for testing: (a) ultrasonic tomograph and (b) type N Schmidt hammer.

The ultrasonic tomograph is designed for testing concrete, reinforced concrete, and stone structures with unilateral access to the tested object in order to evaluate the integrity of its material, detect foreign inclusions, holes, defects, cracks, honeycombs and bars within the material and measure the thickness of objects. The tomograph can test objects up to 2 m thick. The test results are displayed as a cross section (image) type B, which makes it easier to interpret and analyse them. Specialist software makes it possible to reproduce an image from a data file and create a 3D picture of the inner structure. The tomograph has an integrated head, i.e. an antenna array, which includes 48 elements (12 blocks with 4 elements in each block). These are broadband DPC transducers (needing no coupler) of low-frequency transverse waves with a non-abrasive ceramic pad. Each transducer has an independent spring suspension whereby it can be pressed to the tested surface. The head’s nominal operating frequency is 50 kHz [24,25].

Nondestructive tests by means of the ultrasonic tomograph were carried out on the core’s concrete walls by the staircase in 196 measuring places. The tests were conducted in four bands (four measuring points in each band) on the core’s wall by the stairs and in one measuring point on the wall at each flat entrance door. The measurement points on each band were approximately 50 cm apart from each other, counting from the bottom. The lowest point was approximately 20–30 cm above the ceiling level. The authors wanted to obtain images of almost the entire height of the core wall. Exemplary bands with measuring points are shown in Figure 4. The device’s testing depth was set at 750 mm.

Figure 4 
               Location and general denotation of measuring points in the staircase (projection drawing is from the study of Schabowicz et al. [7]).
Figure 4

Location and general denotation of measuring points in the staircase (projection drawing is from the study of Schabowicz et al. [7]).

Nondestructive tests by means of the N-type Schmidt hammer were carried out in order to determine the compressive strength of the concrete. The medium (normal) n-type hammer with an impact load of 2.25 Nm is designed for testing ordinary concrete in precast concrete units and in structures. Schmidt hammers determine the surface hardness of concrete by measuring the rebound of the hammer impact mass. The rebound value, i.e. so-called rebound number R is read off the hammer’s scale. In order to determine the compressive strength of concrete by the sclerometric method using the Schmidt hammer, one must use an empirical f cR relation (between concrete’s compressive strength f c and rebound number R) [22,23]. This relation was determined using the approximate method by matching an empirical basic regression curve to the composition, the concrete making process and the curing, age and moisture content of the concrete. This method has been used in Poland since about 1960, i.e. from the very beginning of the application of NDT methods to concrete strength evaluation [23]. As mentioned earlier, it was not possible to take core drillings from the concrete shaft. Therefore, the empirical relationship was taken from the curves developed by ITB contained in the study of Runkiewicz and Sieczkowski [23] for concrete of similar composition, made at a time similar to that of the construction of the tested object. The tests using the Schmidt hammer were carried out in the selected places marked in Figure 4.

3 Processing of sclerometer measurement results

The measurement results were recorded on special forms (sclerometric measurement logs), appended to this article. The preparation of output data includes calculations of the medians of the readings from the particular testing places. As a result, one obtains n values of R i .

Having n values of R i for a given element (area), the following statistical parameters were calculated [23]:

  • the median of rebound numbers R m ,

  • the standard deviation (s R ) of the medians of the rebound numbers

(1) s R = 1 n 1 i = 1 n ( R i R m ) 2 ,

where the coefficient of variation (ν R ) of the medians of the rebound numbers is calculated from the relation

(2) ν R = s R R m 100 , % ,

where R i is the median of the rebound numbers in the measuring place, R m is the median of the medians of rebound number values in n measuring places, n is the number of measuring places, s R is the standard deviation of rebound numbers R i in n measuring places (points), and ν R is the coefficient of variation of rebound numbers R i in n measuring places (points).

Then, using the parabolic relation f–R mean strength f m (for cylindrical samples) was calculated from the following formula dedicated to type N sclerometers [22]:

(3) f m = R m 0.041 R m ( ν R 2 + 1 ) 0.915 + 7.4 R m MPa .

When calculating the ultimate value of f m , the correction coefficients given in the study of Runkiewicz and Brunarski [22] were applied to take into account the age of the concrete and the degree of moisture accumulation in it.

Then, indicators characterizing concrete quality, such as

  • strength standard deviation s f ,

  • strength variation coefficient ν f , and

  • concrete homogeneity

were determined.

When parabolic relations f–R were used, strength standard deviation s f was calculated (for a type N sclerometer) from the following formula [23]:

(4) s f = R m ν R 0.00336 R m 2 ( ν R 2 + 2 ) 0.150 R m + 0.837 MPa .

The coefficient of variation of concrete strength was calculated using the following formula:

(5) ν f = s f f m 100 , % .

The homogeneity of the concrete was determined on the basis of variation coefficient ν f , using Table 1 [23].

Table 1

Concrete homogeneity rating based on the variation coefficient [23]

Concrete homogeneity rating Strength variation coefficient (ν f)% for ordinary concrete of class
C16/20C20/25 C25/30C45/50
Very good <10 7
Good 11–13 8–10
Medium 14–16 11–13
Satisfactory 17–20 14–15
Unsatisfactory >20 16

The final step in the processing of the results was the evaluation of the characteristic compressive strength of the concrete in the structure. The characteristic compressive strength of the concrete in the structure (f ck,cyl) according to the design standards was determined on the basis of the sclerometric tests as the smaller relation from the following [23]:

(6) f ck , cyl = f m ( n ) , is , R 0.85 1.48 s R ,

(7) f ck , cyl = f is , min , R 0.85 + 4 ,

where f ck,is,R is the characteristic compressive strength of the concrete in the structure, determined on the basis of the sclerometric tests, meeting the design standards; and f m(n),is,R is the mean compressive strength of the concrete in the structure, determined indirectly on the basis of the sclerometric tests.

Knowing the value of f ck,cyl, the strength class of the concrete was determined in accordance with standard PN-EN 206 [26,27].

4 Test results and their analysis

4.1 Tests using ultrasonic tomography

The nondestructive test results (in the form of images) obtained using ultrasonic tomography in all the 196 measuring points are reported in the annex to the study of Schabowicz et al. [7]. For reasons of space, the test results together with their interpretation are presented below for only a few selected measuring points.

Figures 59 show type B images for selected measuring points located on the core wall in the staircase. Figure 10 shows the image for the measuring point located on the side wall at the entrance to a flat on the seventh floor. In the figures, the determined thickness of the concrete wall is indicated by dashed lines and arrows.

Figure 5 
                  Image obtained from tests using ultrasonic tomography in measuring point X2 (between ground and first floors) with indicated determined wall thickness.
Figure 5

Image obtained from tests using ultrasonic tomography in measuring point X2 (between ground and first floors) with indicated determined wall thickness.

Figure 6 
                  Image obtained from tests using ultrasonic tomography in measuring point X4 (between first and second floors) with indicated determined wall thickness.
Figure 6

Image obtained from tests using ultrasonic tomography in measuring point X4 (between first and second floors) with indicated determined wall thickness.

Figure 7 
                  Image obtained from tests using ultrasonic tomography in measuring point X2 (between second and third floors) with indicated determined wall thickness.
Figure 7

Image obtained from tests using ultrasonic tomography in measuring point X2 (between second and third floors) with indicated determined wall thickness.

Figure 8 
                  Image obtained from tests using ultrasonic tomography in measuring point X13 (between seventh and eighth floors) with indicated determined wall thickness.
Figure 8

Image obtained from tests using ultrasonic tomography in measuring point X13 (between seventh and eighth floors) with indicated determined wall thickness.

Figure 9 
                  Image obtained from tests using ultrasonic tomography in measuring point X14 (between ninth and tenth floors) with indicated determined wall thickness.
Figure 9

Image obtained from tests using ultrasonic tomography in measuring point X14 (between ninth and tenth floors) with indicated determined wall thickness.

Figure 10 
                  Image obtained from tests using ultrasonic tomography in measuring point X17 on the side wall at entrance to flat on the seventh floor, with indicated determined wall thickness.
Figure 10

Image obtained from tests using ultrasonic tomography in measuring point X17 on the side wall at entrance to flat on the seventh floor, with indicated determined wall thickness.

An analysis of the obtained images showed that the thickness of the core’s concrete wall varies along the height of the building. The largest core wall thickness, amounting to 350–400 mm, was found at the height between the ground floor and the first floor. At the height between the first floor and the second floor wall thickness amounts to 280–300 m. In the case of the next floors, wall thickness ranges from 140 to 200 mm. It should be noted that the core wall thickness markedly decreases with the building’s height, reaching 140–160 mm. A detailed breakdown of the thickness of the core’s concrete walls is presented in Table 2.

Table 2

Breakdown of core concrete wall thickness determined using ultrasonic tomography

Measuring place Determined wall thickness (mm)
Core wall between ground floor and first floor 350–400
Core wall between first and second floors 280–300
Core wall between second and third floors 180–200
Core wall between third and fourth floors 150–180
Core wall between fourth and fifth floors 150–180
Core wall between fifth and sixth floors 150–180
Core wall between sixth and seventh floors 150–180
Core wall between seventh and eighth floors 150–180
Core wall between eighth and ninth floors 150–180
Core wall between ninth and tenth floors 140–160
Core wall between tenth and eleventh floors 140–160

In the case of the “side” walls in the core, in which there are entrance doors to flats, their thickness was found to range from 140 to 160 mm. Moreover, two control boreholes were drilled through the core’s walls from the staircase, confirming the wall thickness values estimated using ultrasonic tomography.

4.2 Sclerometric test

The sclerometric test results for each of the measuring points are reported in the study of Schabowicz et al. [7]. They are contained in sclerometric measurement logs. For each of the measuring points, the value of f ck,cy was determined, and then the concrete’s strength class in accordance with standard PN-EN 206 [26]. An exemplary measurement log for tests carried out on the core’s concrete wall between the fifth and sixth floors is shown in Figure 11.

Figure 11 
                  Sclerometric measurement log for measuring points located on the core’s concrete wall between the fifth and sixth floors.
Figure 11

Sclerometric measurement log for measuring points located on the core’s concrete wall between the fifth and sixth floors.

An analysis of the results of the sclerometric tests carried out on the core’s concrete walls in 10–20 measuring points along the building’s height from the ground floor to the 11th floor clearly showed a slight variation in the concrete’s compressive strength. For most of the measuring points, the concrete’s strength class determined according to PN-EN 206 [26] is C12/15. In a few places, the test results indicated concrete strength class C16/20 (between fourth and fifth floors, between sixth and seventh floors and between eighth and ninth floors). Namely, small differences in the specific strength of concrete most likely result from the fact that the concrete core was made in a dozen or so stages (described in Section 1). Considering the realities in Poland at that time, it probably occurred that the regimes related to the production and control of the concrete mix were not maintained, hence these differences. However, since in most of the measuring places the concrete strength class was established to be C12/15, it was the latter which was assumed in the structural calculations in the study of Schabowicz et al. [7]. Moreover, one should note that the assumption of an “underestimated” concrete strength provides a larger safety margin during structural calculations, which is particularly important in the case of old structures whose engineering documentation is not available and there is no certainty that their concrete members had been properly made and are characterized by the strength parameters specified in the design. It should be noted that sclerometric tests were conducted not only on the walls of the building’s concrete core but also the core on basement level, the walls under the lift shaft and the concrete columns created by concreting the load-carrying cables as part of the repair in the 1970s were tested.

5 Conclusion

The results of tests carried out on the core of the Trzonolinowiec building located in Wroclaw have been presented. The nondestructive ultrasonic tomography method and the sclerometric method were used for the tests.

The thickness of the unilaterally accessible core of the building was determined using ultrasonic tomography method. An analysis of the images showed that the thickness of the core’s concrete wall varies along the height of the building. The largest core wall thickness, amounting to 350–400 mm, was detected at the height between the ground floor and the first floor. At the height between the first floor and the second floor, the wall thickness amounts to 280–300 m. For the next floors, the wall thickness ranges from 140 to 200 mm. It should be noted that the core wall thickness markedly decreases with the building’s height, reaching 140–160 mm. The tests have clearly showed that the ultrasonic tomography method is highly useful for determining the thickness of unilaterally accessible concrete members.

The tests using the sclerometric method carried out on the concrete walls of the building’s core clearly showed a slight variation in the concrete’s compressive strength. In most of the measuring points, the concrete was found to be of class C12/15. In a few places, the concrete was found to be of class C16/20.

The results obtained by nondestructive testing were then used to build a BIM model of the Trzonolinowiec building. An exemplary visualization and cross sections made in the study of Schabowicz et al. [7] are shown in Figure 12.

Figure 12 
               BIM model: (a) horizontal cross section through building’s typical floor and core on level 3, (b) view from SW, and (c) vertical EW cross section through building [7].
Figure 12

BIM model: (a) horizontal cross section through building’s typical floor and core on level 3, (b) view from SW, and (c) vertical EW cross section through building [7].

One should note that the tests presented in this article were only a part of the tests carried out in the investigated building. All the tests and their results are presented in an extensive building survey report [7]. The test results presented in this study were used in structural calculations. The results of the calculations are very interesting and of critical importance for the further use of this building. They have clearly shown that the building is in imminent failure condition and immediately needs a major overhaul. The tests have provided extensive material for further publications by the researchers taking part in the investigations of the Trzonolinowiec building. In conclusion, the authors would also like to mention that the conducted research may also suggest areas for further research. Namely, the methods used in the study can be successfully applied to the diagnosis of historic buildings. They are particularly recommended when it is not possible to take samples to determine the thickness of the tested elements and to estimate their strength using destructive methods.

  1. Funding information: Authors state no funding involved.

  2. Author contributions: All authors have accepted responsibility for the entire content of this manuscript and consented to its submission to the journal, reviewed all the results, and approved the final version of the manuscript. TG: conducted research and developed results, methodology, writing, visualization, and interpretation. KS: methodology, conceptualization, writing – reviewing and editing, guidance, critical revision, and interpretation.

  3. Conflict of interest: Authors state no conflict of interest.

  4. Data availability statement: The datasets generated during and analysed during the current study are available from the corresponding author on reasonable request.

References

[1] Hoła J, Schabowicz K. State-of-the-art nondestructive methods for diagnostics testing of building structures – anticipated development trends. Arch Civ Mech Eng. 2010;10(3):5–18.10.1016/S1644-9665(12)60133-2Suche in Google Scholar

[2] Bungey J, Millard S, Gratham M. Testing of concrete in structures. London: Taylor & Francis; 2006.10.1201/9781482264685Suche in Google Scholar

[3] Lim MK, Cao H. Combining multiple NDT methods to improve testing effectiveness. Constr Build Mater. 2013;38:1310–5.10.1016/j.conbuildmat.2011.01.011Suche in Google Scholar

[4] https://pl.wikipedia.org/wiki/Trzonolinowiec_we_Wroc%C5%82awiu [Internet]. Trzonolinowiec we Wrocławiu.Suche in Google Scholar

[5] https://architektura.muratorplus.pl/krytyka/tak-powstal-wroclawski-trzonolinowiec-pierwszy-w-polsce-wiezowiec-podwieszony-aa-z4PX-mHFb-5dPN.html [Internet]. Tak powstał wrocławski Trzonolinowiec - pierwszy w Polsce wieżowiec podwieszony.Suche in Google Scholar

[6] https://www.wroclaw.pl/dla-mieszkanca/trzonolinowiec-kosciuszko-jak-budowano-historia-archiwalne-zdjecia [Internet]. Jak Trzonolinowiec zawisł we Wrocławiu i stawiano go od góry do dołu.Suche in Google Scholar

[7] Schabowicz K, Berkowski P, Dmochowski G, Gorzelańczyk T, Noszczyk P, Szóstak M, et al. Survey report concerning the condition of structural components in a residential building at 72 Kosciuszko Street in Wroclaw, determining deficiencies in this condition and a way of remedying them in accordance with the standards specified by the County Building Control Office (PINB) – the duty contained in PINB decision No. 183/2022 (in Polish). Civil Engineering Faculty Reports Series. Wrocław, Poland: Wrocław University of Science and Technology; 2024. Ser. SPR, No.1.Suche in Google Scholar

[8] Attenni M. Informative models for architectural heritage. Heritage. 2019;2(3):2067–89.10.3390/heritage2030125Suche in Google Scholar

[9] Enshassi MA, Al Hallaq KA, Tayeh BA. Limitation factors of building information modeling (BIM) implementation. Open Constr & Build Technol J. 2019;13:189–96.10.2174/1874836801913010189Suche in Google Scholar

[10] Schabowicz K. Ultrasonic tomography–The latest nondestructive technique for testing concrete members–Description, test methodology, application example. Arch Civ Mech Eng. 2014;14(2):295–303.10.1016/j.acme.2013.10.006Suche in Google Scholar

[11] Schabowicz K, Hoła J. Nondestructive elastic-wave tests of foundation slab in office building. Mater Trans. 2012;53(2):296–302.10.2320/matertrans.I-M2011845Suche in Google Scholar

[12] Beutel R, Reinhardt H, Grosse C, Glaubitt A, Krause M, Maierhofer C, et al. Comparative performance tests and validation of NDT methods for concrete testing. J Nondestr Eval. 2008;27(1-3):59–65.10.1007/s10921-008-0037-1Suche in Google Scholar

[13] Garbacz A. Nondestructive investigations of polymer-concrete composites using stress waves – repair efficiency evaluation (in Polish). Prace naukowe. Budownictwo z. 147. Warsaw, Poland: Oficyna Wydawnicza Politechniki Warszawskiej; 2007.Suche in Google Scholar

[14] Bień J, Hoła J, Sadowski L. Modern NDT techniques in diagnostics of transport infrastructure concrete structures. International Workshop on Smart Materials, Structures NDT in Canada 2013 Conference & NDT for the Energy Industry; 2013 Oct 7-10; Calgary, Canada. 2013. https://www.ndt.net/article/ndt-canada2013/content/papers/36_Sadowski_Rev1.pdfSuche in Google Scholar

[15] Saleh IS, Mahdi MS, Ojaimi MF. Destructive and nondestructive testsDestructive and nondestructive tests formulation for concrete containing polyolefin fibers. Open Eng. 2022;12:760–8.10.1515/eng-2022-0363Suche in Google Scholar

[16] Schabowicz K. Methodology for non-destructive identification of thickness of unilaterally accessible concrete elements by means of state-of-the-art acoustic techniques. J Civ Eng Manag. 2013;19(3):325–34.10.3846/13923730.2012.757562Suche in Google Scholar

[17] Samokrutov AA, Kozlov VN, Shevaldykin VG. Ultrasonic testing of concrete objects using dry acoustic contact. Methods, instruments and possibilities. The 5th International Conference “Non-Destructive Testing and Technical Diagnostics in Industry”; 2006 May 16-19. Moscow, Russia: Mashinostroenie; 2006.Suche in Google Scholar

[18] Bishko AV, Samokrutov AA, Shevaldykin VG. Ultrasonic echo-pulse tomography of concrete using shear waves low-frequency phased antenna arrays. 17th World Conference on Non-Destructive Testing; 2008 Oct 25–28; Shanghai, China. Curran Associates, Inc.; 2011. p. 3095–103.Suche in Google Scholar

[19] Gorzelańczyk T, Hoła J, Sadowski Ł, Schabowicz K. Methodology of nondestructive identification of defective concrete zones in unilaterally accessible massive members. J Civ Eng Manag. 2013;19(6):775–86.10.3846/13923730.2013.812577Suche in Google Scholar

[20] Gorzelańczyk T, Schabowicz K. Nondestructive testing of thickness of concrete mine lift shaft shell by means of ultrasonic tomograph. E-J Nondestr Test Ultrason. 2013;6:83–8. http://www.ndt.net/article/defektoskopie2012/papers/83_p.pdf.Suche in Google Scholar

[21] Gorzelańczyk T, Hoła J, Schabowicz K. Nondestructive testing of heat pipe carrying tunnel wall thickness by means of ultrasonic tomograph. E-J Nondestr Test Ultrason. 2013;3:23–8. http://www.ndt.net/article/defektoskopie2011/papers/23_p.pdf.Suche in Google Scholar

[22] Runkiewicz L, Brunarski L. Manual for the use of Schmidt hammers for the nondestructive control of the quality of concrete in a structure (in Polish). Manual No. 210. Wars: ITB; 1977.Suche in Google Scholar

[23] Runkiewicz L, Sieczkowski J. Concrete strength evaluation in structures based on sclerometric methods. Guidance. Warszawa: ITB; 2022.Suche in Google Scholar

[24] https://acs-international.com/product/a1040-mira/ [Internet]. A1040 MIRA - thickness measurement, rebar & flaw detection.Suche in Google Scholar

[25] https://pcb.com.pl/products/tomograf-ultradzwiekowy-%D0%B01040-mira [Internet]. Betonoskop A1040 MIRA – tomograf ultradźwiękowy.Suche in Google Scholar

[26] PN-EN 206. Concrete – Specification, performance, production and conformity.Suche in Google Scholar

[27] Czarnecki L, ed. Concrete according to Standard PN-EN 206-1 – commentary – collaborative work (in Polish). Polski Cement Sp. z o.o.: Cracow; 2004.Suche in Google Scholar

Received: 2024-09-12
Revised: 2024-11-18
Accepted: 2024-12-09
Published Online: 2025-02-12

© 2025 the author(s), published by De Gruyter

This work is licensed under the Creative Commons Attribution 4.0 International License.

Artikel in diesem Heft

  1. Research Article
  2. Modification of polymers to synthesize thermo-salt-resistant stabilizers of drilling fluids
  3. Study of the electronic stopping power of proton in different materials according to the Bohr and Bethe theories
  4. AI-driven UAV system for autonomous vehicle tracking and license plate recognition
  5. Enhancement of the output power of a small horizontal axis wind turbine based on the optimization approach
  6. Design of a vertically stacked double Luneburg lens-based beam-scanning antenna at 60 GHz
  7. Synergistic effect of nano-silica, steel slag, and waste glass on the microstructure, electrical resistivity, and strength of ultra-high-performance concrete
  8. Expert evaluation of attachments (caps) for orthopaedic equipment dedicated to pedestrian road users
  9. Performance and rheological characteristics of hot mix asphalt modified with melamine nanopowder polymer
  10. Second-order design of GNSS networks with different constraints using particle swarm optimization and genetic algorithms
  11. Impact of including a slab effect into a 2D RC frame on the seismic fragility assessment: A comparative study
  12. Analytical and numerical analysis of heat transfer from radial extended surface
  13. Comprehensive investigation of corrosion resistance of magnesium–titanium, aluminum, and aluminum–vanadium alloys in dilute electrolytes under zero-applied potential conditions
  14. Performance analysis of a novel design of an engine piston for a single cylinder
  15. Modeling performance of different sustainable self-compacting concrete pavement types utilizing various sample geometries
  16. The behavior of minors and road safety – case study of Poland
  17. The role of universities in efforts to increase the added value of recycled bucket tooth products through product design methods
  18. Adopting activated carbons on the PET depolymerization for purifying r-TPA
  19. Urban transportation challenges: Analysis and the mitigation strategies for road accidents, noise pollution and environmental impacts
  20. Enhancing the wear resistance and coefficient of friction of composite marine journal bearings utilizing nano-WC particles
  21. Sustainable bio-nanocomposite from lignocellulose nanofibers and HDPE for knee biomechanics: A tribological and mechanical properties study
  22. Effects of staggered transverse zigzag baffles and Al2O3–Cu hybrid nanofluid flow in a channel on thermofluid flow characteristics
  23. Mathematical modelling of Darcy–Forchheimer MHD Williamson nanofluid flow above a stretching/shrinking surface with slip conditions
  24. Energy efficiency and length modification of stilling basins with variable Baffle and chute block designs: A case study of the Fewa hydroelectric project
  25. Renewable-integrated power conversion architecture for urban heavy rail systems using bidirectional VSC and MPPT-controlled PV arrays as an auxiliary power source
  26. Exploitation of landfill gas vs refuse-derived fuel with landfill gas for electrical power generation in Basrah City/South of Iraq
  27. Two-phase numerical simulations of motile microorganisms in a 3D non-Newtonian nanofluid flow induced by chemical processes
  28. Sustainable cocoon waste epoxy composite solutions: Novel approach based on the deformation model using finite element analysis to determine Poisson’s ratio
  29. Impact and abrasion behavior of roller compacted concrete reinforced with different types of fibers
  30. Review Articles
  31. A modified adhesion evaluation method between asphalt and aggregate based on a pull off test and image processing
  32. Architectural practice process and artificial intelligence – an evolving practice
  33. Special Issue: 51st KKBN - Part II
  34. The influence of storing mineral wool on its thermal conductivity in an open space
  35. Use of nondestructive test methods to determine the thickness and compressive strength of unilaterally accessible concrete components of building
  36. Use of modeling, BIM technology, and virtual reality in nondestructive testing and inventory, using the example of the Trzonolinowiec
  37. Tunable terahertz metasurface based on a modified Jerusalem cross for thin dielectric film evaluation
  38. Integration of SEM and acoustic emission methods in non-destructive evaluation of fiber–cement boards exposed to high temperatures
  39. Non-destructive method of characterizing nitrided layers in the 42CrMo4 steel using the amplitude-frequency technique of eddy currents
  40. Evaluation of braze welded joints using the ultrasonic method
  41. Analysis of the potential use of the passive magnetic method for detecting defects in welded joints made of X2CrNiMo17-12-2 steel
  42. Analysis of the possibility of applying a residual magnetic field for lack of fusion detection in welded joints of S235JR steel
  43. Eddy current methodology in the non-direct measurement of martensite during plastic deformation of SS316L
  44. Methodology for diagnosing hydraulic oil in production machines with the additional use of microfiltration
  45. Special Issue: IETAS 2024 - Part II
  46. Enhancing communication with elderly and stroke patients based on sign-gesture translation via audio-visual avatars
  47. Optimizing wireless charging for electric vehicles via a novel coil design and artificial intelligence techniques
  48. Evaluation of moisture damage for warm mix asphalt (WMA) containing reclaimed asphalt pavement (RAP)
  49. Comparative CFD case study on forced convection: Analysis of constant vs variable air properties in channel flow
  50. Evaluating sustainable indicators for urban street network: Al-Najaf network as a case study
  51. Node failure in self-organized sensor networks
  52. Comprehensive assessment of side friction impacts on urban traffic flow: A case study of Hilla City, Iraq
  53. Design a system to transfer alternating electric current using six channels of laser as an embedding and transmitting source
  54. Security and surveillance application in 3D modeling of a smart city: Kirkuk city as a case study
  55. Modified biochar derived from sewage sludge for purification of lead-contaminated water
  56. The future of space colonisation: Architectural considerations
  57. Design of a Tri-band Reconfigurable Antenna Using Metamaterials for IoT Applications
  58. Special Issue: AESMT-7 - Part II
  59. Experimental study on behavior of hybrid columns by using SIFCON under eccentric load
  60. Special Issue: ICESTA-2024 and ICCEEAS-2024
  61. A selective recovery of zinc and manganese from the spent primary battery black mass as zinc hydroxide and manganese carbonate
  62. Special Issue: REMO 2025 and BUDIN 2025
  63. Predictive modeling coupled with wireless sensor networks for sustainable marine ecosystem management using real-time remote monitoring of water quality
  64. Management strategies for refurbishment projects: A case study of an industrial heritage building
Heruntergeladen am 29.10.2025 von https://www.degruyterbrill.com/document/doi/10.1515/eng-2024-0100/html
Button zum nach oben scrollen