Home Physical Sciences Simulation study and experimental results for detection and classification of the transient capacitor inrush current using discrete wavelet transform and artificial intelligence
Article Open Access

Simulation study and experimental results for detection and classification of the transient capacitor inrush current using discrete wavelet transform and artificial intelligence

  • Theerasak Patcharoen , Suntiti Yoomak , Atthapol Ngaopitakkul EMAIL logo and Chaichan Pothisarn
Published/Copyright: April 18, 2018

Abstract

This paper describes the combination of discrete wavelet transforms (DWT) and artificial intelligence (AI), which are efficient techniques to identify the type of inrush current, analyze the origin and possible cause on the capacitor bank switching. The experiment setup used to verify the proposed techniques can be detected and classified the transient inrush current from normal capacitor rated current. The discrete wavelet transforms are used to detect and classify the inrush current. Then, output from wavelet is acted as input of fuzzy inference system for discriminating the type of switching transient inrush current. The proposed technique shows enhanced performance with a discrimination accuracy of 90.57%. Both simulation study and experimental results are quite satisfactory with providing the high accuracy and reliability which can be developed and implemented into a numerical overcurrent (50/51) and unbalanced current (60C) protection relay for an application of shunt capacitor bank protection in the future.

1 Introduction

According to the shunt capacitor banks need to be energized and de-energized (switched-in and switch-out) several times in accordance with the behavior of the system load profile, which it is not stable, these banks are created that the switching transient inrush current when they are switched on. The three-phase overcurrent protection relay (50/51) with short time overcurrent and instantaneous functions shall be applied with the desirable minimum pickup of 135% of nominal phase current for grounded wye banks or 125% for ungrounded banks. The operation delay is set long enough to avoid false trips during switching [1, 2]. In modern IEDs (Intelligent Electronic Devices), the time overcurrent functions with fundamental frequency band-pass filters are not sensitive to inrush currents. Successful operation of modern IEDs may be obtained by setting instantaneous relays at a lower value compared with relays without band-pass filters; typically, 3 to 4 times the capacitor bank rated current is sufficient to override back-to-back bank switching [1, 2]. Practically, the minimum pickup is around 15 times the capacitor bank rated current (without band-pass filters) which there is less than the rated short-circuit of the system. It is enough to avoid the relay mal-operation from transient inrush current during energizing the reactive power. However, the suitable pickup setting for instantaneous function shall be 3 to 4 times of the capacitor bank rated current and a few cycles delay because it is convenient for protecting the capacitor in case of the harmonic current presence in the system [3]. Therefore, when designing the shunt capacitor bank protection scheme, it is very important to clearly discriminate between the normal capacitor current and transient capacitor inrush current due to capacitor energizing.

Works of literature on transient classification and discrimination techniques were presented in recent publications [4, 5, 6, 7, 8, 9, 10, 11]. These papers have explained a new method for detecting and classifying the power quality disturbance both industries and utilities. The transient classification using various techniques, for instance, using S-Transform and Competitive Neural Network [5], Mathematic morphology [7, 8], Continuous wavelet transform [9], Decision Tree-based Classifiers and Hidden Markov Model [10] and Wavelet-fuzzy logic [11]. The several results of their literatures are effectively detected and classify the transient inrush current from other events. On the other hand, many kinds of literature provide the technique to classify the transient by obtaining the inrush current signal from switching capacitor bank with only a series reactor. Some literatures simulated only the single step switching. It is not enough and does not cover all of the protection schemes. Additionally, some researchers need the voltage signal to investigate the transient oscillation for discriminating the transient capacitor switching. In the meanwhile, the problem of classification and discrimination transient inrush current remains as an open problem for better discussing and improving the solutions. However, the techniques to detect, classify and discriminate the transient inrush current which is occurred from the 6-difference cases of the transient mitigation methods were not presented.

Therefore, this paper proposes a new technique for detection and classification of the high transient inrush current with the 6-difference cases of transient mitigation methods (for instance, pre-insertion resistor, pre-insertion inductor, current limiting reactor, 6% reactor and synchronous closing control) which are normally found in the application of capacitor bank. The DWT is performed to extract the high-frequency component which is contained in the transient inrush currents. The wavelet coefficients of the scale 1-30 from the DWT will be used for detection. Then, the standard deviation of wavelet scale coefficient will be determined for classifying the possible case of normal switching (isolated) or back-to-back capacitor switching [4]. The total case studies of 244 cases have been tested and verified with various 12 switching inception angles. The results from DWT are an input to the Artificial Intelligence (AI). The type of intelligence is a “Fuzzy Inference System (FIS)”. In order to discriminate the transient inrush current which is occurred from the 6-difference cases of the transient mitigation methods will be used by the fuzzy inference system. The results show that the proposed technique can effectively perform the detection, classification and discrimination of the transient inrush current during capacitor switching which provides the high accuracy more than 90%. It can be developed to overcurrent (50/51) and unbalanced current (60C) protection relay for avoiding the relay mal-operation from high transient inrush current in the future. In addition, the proposed methods can help an engineer who works in the field of protective relay to identify the type of transient signals.

2 System simulation study

2.1 System modeling

The substation shunt capacitor bank used as a model is shown in Figure 1 [12]. The 4th-steps capacitor bank which is rated 72 Mvar, 230 kV is used to simulate the high transient inrush current and classify the possible cases of switching. The three-phase voltage source model is represented by equivalent circuit with a short circuit value of 10 kA [4]. The transient mitigation method for 6-difference cases was numerically simulated: a base-case, with a pre-insertion resistor, with a pre-insertion inductor, with a current limiting reactor, with a series 6% reactor and using synchronous closing control [3]. The inrush current with variation of the inception angle for capacitor bank switching at 0, 30, 60, 90, 120, 150, 180, 210, 240, 270, 300 and 330 degrees were recorded. The switching transient patterns were varied into 6 different cases as following:

Figure 1 The system used in this simulation studies in case of isolated and back-to-back capacitor switching transients [12]
Figure 1

The system used in this simulation studies in case of isolated and back-to-back capacitor switching transients [12]

  1. Simulations using a base case (uncontrolled transient energization)

  2. Simulation using the pre-insertion resistors; each with a resistance value of approximately 86 Ω.

  3. Simulation using the pre-insertion inductors; each with a reactance value of approximately 119 mH.

  4. Simulations using the current limiting reactors; each with inductance value of approximately 1 mH/phase.

  5. Simulations using the series 6% reactors; each with an inductance value of approximately 166 mH per phase.

  6. Simulations using synchronous closing control for the controlled shunt capacitor bank.

2.2 High transient inrush current

To design a protection scheme of capacitor bank able to detect and classify the transient inrush current. Each kind of transient inrush current is very important to be prepared. The PSCAD/ EMTDC [13] was used for simulation by using the sampling frequency of 250 kHz. These recorded signals were used to be an input for wavelet analysis. The example of high transient inrush current form 6-difference cases of transient mitigation methods was shown in Figure 2.

Figure 2 High transient inrush current which is energized by the capacitor bank in 4th-step switching (back-to-back switching) [4]
Figure 2

High transient inrush current which is energized by the capacitor bank in 4th-step switching (back-to-back switching) [4]

The inrush current has been increased while the last step switching. The typical amplitude of the inrush current for back-to-back energization is several kAs with a frequency of more than 2 kHz. The magnitude and frequency of this inrush current is, therefore, much higher than that of an isolated bank. Generally, the isolated capacitor bank switching has an inrush frequency between 300 Hz to 2 kHz and not exceed 20 times of capacitor rated current because the large impedance of network can reduce this inrush current.

3 Proposed techniques

3.1 Discrete wavelet transform for detection and classification

The discrete wavelet transforms based on Daubechis wavelet has been used to detect and classify the high transient inrush current [14]. Figure 3 shows the structure of the proposed techniques for the transient inrush current classifier. The structure is composed of the discrete wavelet transform, wavelet scale analysis, maximum scale selection and transient classification from the inrush current 6-difference cases of transient mitigation methods in order to investigate the possible cause of capacitor bank switching. The DWT is used to analyze the transient signal at scale selecting between 1 to 30 scales only. The mother wavelet, db4 is also used to analyze the transient disturbance owing to less time requirement to do the calculation and provide the classification more correctly than others [10]. The wavelet coefficient from each scale will be determined by Equation (1) [15, 16]. The discrete wavelet transforms (DWT) is used to analyze the transient signal at scale selecting from first scale to thirty scales only.

Figure 3 The structure of transient inrush current detection and classification system with DWT
Figure 3

The structure of transient inrush current detection and classification system with DWT

Eψ(s)=m=0n|DWT(m,n)|2(1)(1)

The wavelet coefficient in each phase during capacitor switching will be conducted for detection the high transient inrush current by using an if-then statement which will be compared with the wavelet coefficient during capacitor rated current (threshold, steady state) as follows.

If (IA, max) > (1.3xThreshold),1,0),

If (IB, max) > (1.3xThreshold),1,0),

If (IC, max) > (1.3xThreshold),1,0),

If (Imax, positive) > (1.3xThreshold),1,0)

and

If (AND (Imax, positive) = 1,

SUM (IA:IB:IC, max) ≥ 2),“Abnormal”,“Normal”)

The above if-then statement is designed to match the high transient inrush current phenomena and the philosophy of the protective relay setting accordance with IEC 60871-1:2014, IEC 60871-3:2015, IEEE Std. 1036-2010 and IEEE Std. C37.99-2012. The capacitor units shall be suitable for continuous operation at an r.m.s. current of 1.30 times the normal rated current that occurs at rated sinusoidal voltage and rated frequency, excluding transients. Therefore, for banks with separate overload and short-circuit protection, the overload protection is normally set in the range of 1.3 and 1.4 times rated current. The operating delay time is set long enough to avoid false trips during switching. The short-circuit protection is set above 3In and a few cycles delay. Refer to the if-then statement as above, the 130% or 1.3 times is from the maximum of capacitor overloading condition. If current phase A, B, C and positive sequence current are higher than the 1.3 times. It is a risk for capacitor damage and exposure due to capacitor overloading. This criterion is the pick-up current setting for overcurrent relay protection. During capacitor switching to close state, the transient inrush current phase A, B, C and positive sequence current will be increased rapidly and higher than the threshold. Therefore, the result of a proposed algorithm is the abnormal condition. Moreover, if the summation of wavelet coefficient of the positive sequence current is higher than the threshold and the summation of wavelet coefficient in each phase can detect more than 2 phases. We can conclude that these signals are abnormal. The criteria of the summation of wavelet coefficient in phase A, B and C shall be used equally or more than 2-phase detection because some of the switching devices are closed nearly to 0 degrees. Thus, the inrush current is very low signal. However, we cannot judge the transient signal whether it is the inrush current switching or normal capacitor rated current. The algorithm of standard deviation will be performed in order to find the type of these transients.

In the section of classification algorithm, the standard deviation is very important features to distinguish the transient disturbance classification [9]. Therefore, the equation to calculate the standard deviation is shown in Equation (2).

σ=1Ns=1N(Eψ(s)μ)2(2)(2)

The standard deviation of the discrete wavelet scale analysis and the number of maximum scales to detect in wavelet scale analysis can be used to classify the possible cause and origin of transient inrush current both isolate and back-to-back capacitor switching by using the if-then statement. The flowchart diagram of the proposed algorithm can be shown in Figure 4.

Figure 4 Flowchart diagram for detection and classification by using the discrete wavelet transforms
Figure 4

Flowchart diagram for detection and classification by using the discrete wavelet transforms

IF (AND (STDEV, inrush, positive) > (1.3*STDEV, threshold, positive), Wavelet, scale max < (Wavelet, scale threshold), “Normal switching”,“Back-to-Back switching”)

As the above algorithm, the standard deviation must be multiplied with 1.30 times to be setting the pick-up current (threshold). The capacitor unit can withstand for continuous operation at an r.m.s. current of 1.30 times the normal rated current that occurs at rated sinusoidal voltage and rated frequency, excluding transients. The variable “STDEV, inrush, positive” is the standard deviation which is calculated from the wavelet coefficient of positive sequence current by using the equation (2). This variable will be calculated the standard deviation totally 30 scale wavelet analysis. The variable “STDEV, threshold, positive” is the standard deviation which is calculated from wavelet coefficient of positive sequence current during normal capacitor switching totally 30 scale wavelet analysis.

3.2 Fuzzy logic inference system for discrimination

To solve the protective relay of capacitor bank mal-operation from transient switching inrush current, a fuzzy-based approach is proposed. The fuzzy logic rules evaluate the multi-resolution features as well as electric characteristics in order to identify the power quality disturbances in network. The fuzzy inference system with two linguistic variables that defines 2-concept, the maximum wavelet scale detection is acted as input 1, the standard deviation is acted for input 2. Then, the output is the type of 6-difference cases for transient mitigation methods. The structure of fuzzy classifier based on the fuzzy inference system (FIS) diagram for discrimination of high transient inrush current is shown in Table 1.

Table 1

Discrimination system based on fuzzy inference – Mamdami rules

Before building the fuzzy interference system, the standard deviation will be multiplied by 100 in order to easily create the membership function and can be designed a system cable of detecting and classifying the high transient inrush current as shown in Figure 5. A fuzzy inference system (FIS) is a system that uses fuzzy set theory to map inputs to outputs. Type of fuzzy inference system which is Mamdani [17, 18]. Mamdani’s fuzzy inference method is the most commonly seen fuzzy methodology using fuzzy set theory. The Mamdani type rules to discriminate the information provided by the two linguistic variable inputs. Figure 6 shows the block diagram of transient inrush current discrimination with FIS scheme based on Mamdani type rules.

Figure 5 The flowchart diagram for transient inrush current discrimination by using fuzzy rules
Figure 5

The flowchart diagram for transient inrush current discrimination by using fuzzy rules

Figure 6 The block diagram of transient inrush current discrimination with Fuzzy inference schemes based on Mamdani type rules
Figure 6

The block diagram of transient inrush current discrimination with Fuzzy inference schemes based on Mamdani type rules

3.3 Experiment test unit

A single line diagram of the experimental test unit is shown in Figure 8. The power supply of the system is taken from the university laboratory at a voltage level of 380 V and then connecting to a step-up voltage transformer to be 415 V. The switching capacitor in each step uses the magnetic contactors k1, k2, and k3. The switched capacitor bank can be operated by push button and a power factor controller (PFR). The HRC fuses will be mainly used for short-circuit protection.

Figure 7 Example of the fuzzy inference surface viewer based on Mamdani type in case of back-to-back capacitor switching
Figure 7

Example of the fuzzy inference surface viewer based on Mamdani type in case of back-to-back capacitor switching

Figure 8 A single line diagram for experimental test unit in laboratory
Figure 8

A single line diagram for experimental test unit in laboratory

The current transformer connected to main incoming phase A to be an input of the controller. The three-phase PQ analyzer is used to do the measurement of the voltage at main bus-bar and transient inrush current in each step. The 3-step capacitor switching will have the reactive power at 5.0 kvar per step including the series 7% reactor. The inductance rating of series reactor is 0.653 mH per phase. The shunt capacitor bank series with the 7% reactor can be used in high distribution loads (loads with more than 4-steps of capacitor banks) and in industrial applications. The inductor size is normally estimated by 7% of the capacitive reactance of the capacitor bank. The picture of experimental test unit is shown in Figure 9.Voltage and current were measured at a location in the front of the magnetic contactor. The measurement of the oscillation overvoltage and high transient inrush current was done using a power quality analyzer. However, the operation of a capacitor bank in experiment test unit will be controlled by manual mode via push button in the front side of the unit.

Figure 9 Photography of the experimental test unit in a university laboratory
Figure 9

Photography of the experimental test unit in a university laboratory

The controller unit receives voltage and current measurements from the potential transformer (PT) and current transformer (CT) to calculate the power factor of the system and then compares these data with the power factor value that is set inside the unit. After that, it sends an on/off signal to the magnetic contractor to close or open the capacitor bank circuit in each step. This test setup is downscale from the capacitor bank system in the 115-kV substation with a reactive power of 48 MVar in each step. This experimental test unit is downscaled from 115 kV to 415 V in the laboratory by using per-unit calculation to determine the size of the capacitor and other devices or equipment for the test unit.

4 Simulation of the proposed algorithm

4.1 Inrush current detection and classification using DWT

The isolated capacitor bank switching provides the maximum wavelet coefficient as the ninth scale (1st step switching). In the meanwhile, the back-to-back capacitor switches as the third scale only. This characteristic will be used to classify the transient inrush current in order to find the possible causes and origin of transient inrush current. The comparison of the wavelet scale coefficients is shown in Figures 1013. The comparison of the wavelet scale coefficients by Equation (1) is considered as illustrated in Figures 12 and 13. As in the figure, the wavelet scale analysis of all step capacitor switching is plotted on the wavelet scale versus wavelet coefficient. The wavelet scale coefficient in case of the threshold obtained from discrete wavelet transform during capacitor was already energized for a period more than 100 msec. It means that the capacitor current is in a stable stage.

Figure 10 The wavelet scale analysis for detection & classification the transient inrush current in case capacitor bank the 1st-step switching (base case)
Figure 10

The wavelet scale analysis for detection & classification the transient inrush current in case capacitor bank the 1st-step switching (base case)

Figure 11 Maximum wavelet scale analysis for transient inrush current in case of the 4th-step switching with the 6-different cases of transient reduction control
Figure 11

Maximum wavelet scale analysis for transient inrush current in case of the 4th-step switching with the 6-different cases of transient reduction control

Figure 12 The transient inrush current in maximum wavelet scale analysis for all the step capacitor bank switching in case of base case (no transient control)
Figure 12

The transient inrush current in maximum wavelet scale analysis for all the step capacitor bank switching in case of base case (no transient control)

Figure 13 The maximum of wavelet scale analysis and standard deviation of 30 scale wavelet coefficients for all step capacitor bank switching in the base case (with series current limiting reactor 1.0 mH)
Figure 13

The maximum of wavelet scale analysis and standard deviation of 30 scale wavelet coefficients for all step capacitor bank switching in the base case (with series current limiting reactor 1.0 mH)

4.2 Inrush current discrimination using Fuzzy Inference

The discrimination system was tested with 244 cases of transient inrush current signals which were generated with the PSCAD simulation. Due to the standard deviation for linguistic variables input 2 is very low. So, they will be multiplied by 100 in order to easy for create the membership functions and Mamdani rules in FIS. In Figure 11, the maximum wavelet scale detection is a triangular membership function defined as input 1. The standard deviation is a trapezoidal membership function defined as input 2. Then, the output is as a triangular membership function.

The scheme of FIS can be shown in Figure 14. Index of membership function for first and second input are defined by triangular (trimf) and trapezoidal (trapmf) respectively. Output is represented by a triangular (trimf). The surface viewer is shown as in Figure 14. A three-dimensional curve represents the mapping from maximum wavelet scale detection (input1) and standard deviation (input2) to the type of transient reduction control (output). The fuzzy rules for isolated and back-to-back capacitor switching will be established by Mamdani 21-rule and Mamdani 35-rule respectively.

Figure 14 Definition of the membership functions in case of back-back switching
Figure 14

Definition of the membership functions in case of back-back switching

4.3 Experimental test set

For the experiment, the system’s normal case has been recorded to evaluate switching transients occurred when the energized capacitor back phenomena taken into account are inrush current and voltage transients. The current signals measurement will be acted as input for wavelet transform in order to verify the proposed algorithm. The inrush current waveform and oscillation overvoltage at the bus are shown in Figure 15 and 16, respectively. In the case of a capacitor bank system without an installed reactor (base case), when considering the system current after switching in the first step, the inrush current magnitude rises to approximately 7-8 times the normal current magnitude due to the energizing current to the capacitor bank. Inrush current in the next step is higher than the previous one due to the inrush current occurring when the energizing capacitor bank combines with the current from the energized bank. It causes an increase in magnitude of the inrush current accordance with the theory.

Figure 15 The 3-phase inrush current waveform measured by the PQ analyzer in a university laboratory
Figure 15

The 3-phase inrush current waveform measured by the PQ analyzer in a university laboratory

Figure 16 The transient inrush current and voltage at bus signals from an experimental result when the 2nd-step switching with series 7% reactor
Figure 16

The transient inrush current and voltage at bus signals from an experimental result when the 2nd-step switching with series 7% reactor

In Figure 15, the inrush current signal for phase A, B, and C will be calculated to determine the symmetrical component of positive, negative and zero sequence. The positive sequence current of each phase will be acted an input of discrete wavelet transform to detect and classify the transient inrush current behavior as shown in Figure 17. Then, the output from wavelet classifier will be used to input for fuzzy inference for discrimination the type of transient reduction control between base case and 7% reactor. The wavelet scale analysis to detect and classify the signals whether transient created from isolated switching or back-to-back switching was shown in Figure 17. The result shows that maximum wavelet coefficient can be founded in the 2nd scale.

Figure 17 The wavelet scale analysis for detection and classification of the transient inrush current in case capacitor bank the 1st-step switching (experimental – 7% reactor).
Figure 17

The wavelet scale analysis for detection and classification of the transient inrush current in case capacitor bank the 1st-step switching (experimental – 7% reactor).

The fuzzy inference system for discriminating the type of transient mitigation method in case of an experimental test unit can be built in the same method as the simulation study case. But the membership function for output variable is different. It is only 2-output between 7% reactor and base case. The maximum wavelet scale detection is a triangular membership function defined as input 1. The standard deviation is a trapezoidal membership function defined as input 2. Then, the output is as a triangular membership function.

5 Results of proposed algorithm

5.1 Simulation study results

The proposed algorithm has shown satisfactory performance to detect, classify and discriminate the transient inrush current in the various types of capacitor switching transient. The errors of an algorithm will have occurred when switching at reference voltage phase A as 0 degree and 180 degrees because this switching inception angle provides the zero voltage across the circuit breaker [4]. So, the transient inrush current does not occur.

5.2 Experimental results

The experimental results are shown in Table IV and V. The proposed algorithm shows excellent performance to detect, classify and discriminate the high transient inrush current.

The results of the proposed algorithm were shown in Table 2, 3, 4 and 5 respectively. The wavelet coefficient corresponds with the switching sequence. The wavelet coefficient will be increased when the number of step-switching is increased. The last step-switching provides the highest of wavelet coefficient which is corresponding with the inrush current in the system as the capacitor switching theory (Isolated & Back-to-Back capacitor switching). Each of the wavelet coefficient from the 6-difference cases of transient reduction control can be found that the switching capacitor bank without transient reduction control (base case) have the highest value of wavelet coefficient, but the maximum of wavelet scale detection is very minimum. In the meanwhile, the switching capacitor bank with synchronous closing control has the lowest value of wavelet coefficient, but the maximum of wavelet scale detection is so high. It is concluded that if the maximum of wavelet scale analysis is high, the inrush current is very low. Contrarily, if the maximum of wavelet scale analysis is very low, it has the meaning that the inrush current is very high. On the other hand, if the wavelet coefficient is so high, the inrush current is so high too. Therefore, the wavelet coefficient value is corresponding with the high transient inrush current signal by the wavelet coefficient which will be highest value when the capacitor bank switching in the last step. Regarding the fuzzy inference system, it shows the high accuracy to discriminate the high transient inrush current in case of the transient mitigation method of synchronous switching control and pre-insertion inductor respectively. In the meanwhile, the pre-insertion resistor has the highest of error discrimination because each of transient mitigation method that provided with the value of standard deviation and max scale detection had nearly value in each mitigation method. It is quite difficult to discriminate the type of transient mitigation method with FIS. However, the proposed algorithm provides the accuracy more than 90% for classifying the all capacitor switching transient inrush currents.

Table 2

Detection and classification using DWT

Type of inrush currentPerformance Conclusion for Inrush Current Classification% Accuracy
1st-Step2nd-Step3rd-Step4th-Step
Base CaseNSBBSBBSBBS100%
PIRNSBBSBBSBBS100%
PIINSBBSBBSBBS100%
CLRNSBBSBBSBBS100%
6% ReactorNSBBSBBSBBS100%
SW SynNSNSNSNS100%
  1. Note:

    NS = Normal switching

    BBS = Back-to-back switching

Table 3

Discrimination using fuzzy inference system

Type of inrush currentNo. eventTransients inrush current signalsErrors %Acc.
Base casePIRPIICLR6% REASW SYN
Base case484300500589.58
PIR4803734401177.08
PII4800480000100.00
CLR482004510393.75
6% Reactor480020442491.67
SW Syn40000040100.00
ALL Transients244 cases
PerformanceISOLATED CAPACITOR SWITCHING 78.69%
BACK-TO_BACK CAPACITOR SWITCHING 94.54%
ALL CAPACITOR SWITCHING TRANSIENTS 90.57%

Table 4

Detection and classification using DWT

Type of inrush currentPerformance conclusion for inrush current classification% Accuracy
1st-Step2nd-Step3rd-Step
Base CaseNSBBSBBS100%
7% ReactorNSBBSBBS100%
  1. Note: NS = Normal switching

    BBS = Back-to-back switching

Table 5

Discrimination using fuzzy inference system

Type of inrush currentNo. eventsTransients inrush current signalsErrors% Accuracy
Base case7% Reactor
Base case3300100.00
7% Reactor3030100.00
ALL Transients    6 cases
PerformanceISOLATED CAPACITOR SWITCHING 100%
BACK-TO_BACK CAPACITOR SWITCHING 100%
ALL CAPACITOR SWITCHING TRANSIENTS 100%

6 Conclusion

This paper presents the technique of detection, classification and discrimination of the high transient inrush current during capacitor bank switching occurring on the substation shunt capacitor bank in order to avoid the overcurrent relay (50/51) and unbalanced current relay (60C) mal-operation due to failed trip from high transient inrush current. This paper described the approach to detect and classify high transient inrush current, which occurs from the energization of an HV substation shunt capacitor bank, rated 4×72 Mvar/230 kV, in a Thailand’s substation system. The main purpose of the new algorithm in this paper is clear to discriminate between the normal capacitor current and transient capacitor inrush current only. The protective relay can be known that the type of transient signals is the inrush current or normal capacitor rated current. Thus, the relay will not be tripped (block function) from the type of transient inrush current signal.

PSCAD/EMTDC was used to simulate transient inrush current with the transient mitigation methods in six different cases. Wavelet scale analysis can be used to detect and classify the possible cause of transient inrush current both isolate and back-to-back capacitor switching. The type of Artificial intelligence is a Fuzzy Inference System which will be used to discriminate and distinguish the type of capacitor switching in the 6-different cases of transient reduction control. The proposed techniques show the highest accuracy and satisfaction for detection, classification and discrimination in both the experimental test unit and simulation study. It can be developed to the numerical protective relay in the protection scheme of the HV shunt capacitor bank.

However, the next research will be a further study on how to discriminate between short-circuit current and inrush current signals. The protection algorithm will be conducted. Finally, the author expected that the software engineer who was responsible to develop the computer processor in IED have an idea to classify the type of transient signal during capacitor switching.

Acknowledgement

The authors wish to acknowledge the financial support for this research (No. KREF045507) from the King Mongkut’s Institute of Technology Ladkrabang research fund, Thailand.

References

[1] IEEE Standard 1036, IEEE Guide for Application of Shunt Power Capacitors, 2010.Search in Google Scholar

[2] IEC Standard 60871-1, Shunt Capacitors for A.C. Power Systems Having a Rated Voltage above 1000V – Part 1: General, 2014.Search in Google Scholar

[3] IEEE Standard C37.99, IEEE Guide for the Protection of Shunt Capacitor Banks, 2006.Search in Google Scholar

[4] Patcharoen T., Ngaopitakkul A., Pothisarn C., Leelajindakrairerk M., Simulation analysis of the switching of 230 kV substation shunt capacitor banks with a 6% series reactor for limiting transient inrush currents and oscillation overvoltage, Electrical Engineering (2017), (in press), 10.1007/s00202-017-0516-4.Search in Google Scholar

[5] Mokryani G., Siano P., Piccolo A., Detection of Inrush Current Using S-Transform and Competitive Neutral Network, International Conference on Optimization of Electrical and Electronic Equipment (OPTIM) (20-22 May 2010, Brasov, Romania, Romania), IEEE, 2010, 191-196.10.1109/OPTIM.2010.5510420Search in Google Scholar

[6] Farias P.E., de Morais A.P., Cardoso G., Oliveira A.L., Transients Detection and Classification in Distribution Networks for High Impedance Faults Identification, International Universities Power Engineering Conference (UPEC) (2-5 September 2014, Cluj-Napoca, Romania), IEEE, 2014, 1-6.10.1109/UPEC.2014.6934774Search in Google Scholar

[7] Buggaveeti S.K., Brahma S.M., A Morphological Filter to Distinguish a Fault from Capacitor Switching, IEEE PES Transmission and Distribution Conference and Exposition (19-22 April 2010, New Orleans, LA, USA), IEEE, 2010, 1-5.10.1109/TDC.2010.5484367Search in Google Scholar

[8] Buggaveeti S.K., Brahma S.M., Improved Overcurrent Protection of Capacitor Banks Using Mathematical Morphology, IEEE Transactions on Power Delivery, 2011, 26, 3, 1972-1979.10.1109/TPWRD.2011.2120630Search in Google Scholar

[9] Tan R.H.G., Ramachandaramurthy V.K., Capacitor Bank Switching Classification using Scale Selection Continuous Wavelet Transform, International Conference on Power Electronics and Drive Systems (2-5 November 2009, Taipei, Taiwan), IEEE, 2009, 950-955.10.1109/PEDS.2009.5385785Search in Google Scholar

[10] Perera N., Rajapakse A.D., Power System Transient Classification for Protection Relaying, International Conference on Harmonics and Quality of Power (28 September -1 October 2008, Wollongong, NSW, Australia), IEEE, 2008, 1-6.10.1109/ICHQP.2008.4668826Search in Google Scholar

[11] Chacon M. I., Duran J.L., Santiesteban L.A., A Wavelet-Fuzzy Logic Based System to Detect and Identify Electric Power Disturbances, IEEE Symposium on Computational Intelligence in Image and Signal Processing (IEEE CIISP (2007) (1-5 April 2007, Honolulu, HI, USA), 52-57.10.1109/CIISP.2007.369293Search in Google Scholar

[12] Transmission System Operation Planning Department, Switching and Transmission Line Diagram, Electricity Generation Authorization Thailand Press., Thailand, 2010.Search in Google Scholar

[13] Manitoba HVDC Research Centre, EMTDC: Transient Analysis for PSCAD Power System Simulation, Manitoba HVDC Research Centre Inc., Manitoba, Canada, 2003.Search in Google Scholar

[14] Masoum M.A.S., Jamali S., Ghaffarzadeh N., Detection and classification of power quality disturbances using discrete wavelet transform and wavelet networks, IET Science, Measurement & Technology, Measurement and Technology, IET, 2010, 4, 193-205.10.1049/iet-smt.2009.0006Search in Google Scholar

[15] Rodrfguez A., Aguado J., Martin F., Mufioz J., Medina M., Ciumbulea G., Classification of Power Quality Disturbances using Wavelet and Artificial Neural Network, International Conference on Power System Technology (POWERCON) (24-28 October 2010, Hangzhou, China), IEEE, 2010, 14-7.10.1109/POWERCON.2010.5666537Search in Google Scholar

[16] Wavelet Toolbox User’s Guide (R2016a), MathWorks, Inc., 2016.Search in Google Scholar

[17] Fuzzy Logic Toolbox User’s Guide (R2016a), MathWorks, Inc., 2016.Search in Google Scholar

[18] Mielczarski W., Fuzzy Logic Techniques in Power Systems, Physica-Verlag Heidelberg, 1998Search in Google Scholar

Received: 2017-11-01
Accepted: 2017-11-30
Published Online: 2018-04-18

© 2018 Theerasak Patcharoen et al., published by De Gruyter

This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 License.

Articles in the same Issue

  1. Regular Articles
  2. A modified Fermi-Walker derivative for inextensible flows of binormal spherical image
  3. Algebraic aspects of evolution partial differential equation arising in the study of constant elasticity of variance model from financial mathematics
  4. Three-dimensional atom localization via probe absorption in a cascade four-level atomic system
  5. Determination of the energy transitions and half-lives of Rubidium nuclei
  6. Three phase heat and mass transfer model for unsaturated soil freezing process: Part 1 - model development
  7. Three phase heat and mass transfer model for unsaturated soil freezing process: Part 2 - model validation
  8. Mathematical model for thermal and entropy analysis of thermal solar collectors by using Maxwell nanofluids with slip conditions, thermal radiation and variable thermal conductivity
  9. Constructing analytic solutions on the Tricomi equation
  10. Feynman diagrams and rooted maps
  11. New type of chaos synchronization in discrete-time systems: the F-M synchronization
  12. Unsteady flow of fractional Oldroyd-B fluids through rotating annulus
  13. A note on the uniqueness of 2D elastostatic problems formulated by different types of potential functions
  14. On the conservation laws and solutions of a (2+1) dimensional KdV-mKdV equation of mathematical physics
  15. Computational methods and traveling wave solutions for the fourth-order nonlinear Ablowitz-Kaup-Newell-Segur water wave dynamical equation via two methods and its applications
  16. Siewert solutions of transcendental equations, generalized Lambert functions and physical applications
  17. Numerical solution of mixed convection flow of an MHD Jeffery fluid over an exponentially stretching sheet in the presence of thermal radiation and chemical reaction
  18. A new three-dimensional chaotic flow with one stable equilibrium: dynamical properties and complexity analysis
  19. Dynamics of a dry-rebounding drop: observations, simulations, and modeling
  20. Modeling the initial mechanical response and yielding behavior of gelled crude oil
  21. Lie symmetry analysis and conservation laws for the time fractional simplified modified Kawahara equation
  22. Solitary wave solutions of two KdV-type equations
  23. Applying industrial tomography to control and optimization flow systems
  24. Reconstructing time series into a complex network to assess the evolution dynamics of the correlations among energy prices
  25. An optimal solution for software testing case generation based on particle swarm optimization
  26. Optimal system, nonlinear self-adjointness and conservation laws for generalized shallow water wave equation
  27. Alternative methods for solving nonlinear two-point boundary value problems
  28. Global model simulation of OH production in pulsed-DC atmospheric pressure helium-air plasma jets
  29. Experimental investigation on optical vortex tweezers for microbubble trapping
  30. Joint measurements of optical parameters by irradiance scintillation and angle-of-arrival fluctuations
  31. M-polynomials and topological indices of hex-derived networks
  32. Generalized convergence analysis of the fractional order systems
  33. Porous flow characteristics of solution-gas drive in tight oil reservoirs
  34. Complementary wave solutions for the long-short wave resonance model via the extended trial equation method and the generalized Kudryashov method
  35. A Note on Koide’s Doubly Special Parametrization of Quark Masses
  36. On right-angled spherical Artin monoid of type Dn
  37. Gas flow regimes judgement in nanoporous media by digital core analysis
  38. 4 + n-dimensional water and waves on four and eleven-dimensional manifolds
  39. Stabilization and Analytic Approximate Solutions of an Optimal Control Problem
  40. On the equations of electrodynamics in a flat or curved spacetime and a possible interaction energy
  41. New prediction method for transient productivity of fractured five-spot patterns in low permeability reservoirs at high water cut stages
  42. The collinear equilibrium points in the restricted three body problem with triaxial primaries
  43. Detection of the damage threshold of fused silica components and morphologies of repaired damage sites based on the beam deflection method
  44. On the bivariate spectral quasi-linearization method for solving the two-dimensional Bratu problem
  45. Ion acoustic quasi-soliton in an electron-positron-ion plasma with superthermal electrons and positrons
  46. Analysis of projectile motion in view of conformable derivative
  47. Computing multiple ABC index and multiple GA index of some grid graphs
  48. Terahertz pulse imaging: A novel denoising method by combing the ant colony algorithm with the compressive sensing
  49. Characteristics of microscopic pore-throat structure of tight oil reservoirs in Sichuan Basin measured by rate-controlled mercury injection
  50. An activity window model for social interaction structure on Twitter
  51. Transient thermal regime trough the constitutive matrix applied to asynchronous electrical machine using the cell method
  52. On the zagreb polynomials of benzenoid systems
  53. Integrability analysis of the partial differential equation describing the classical bond-pricing model of mathematical finance
  54. The Greek parameters of a continuous arithmetic Asian option pricing model via Laplace Adomian decomposition method
  55. Quantifying the global solar radiation received in Pietermaritzburg, KwaZulu-Natal to motivate the consumption of solar technologies
  56. Sturm-Liouville difference equations having Bessel and hydrogen atom potential type
  57. Study on the response characteristics of oil wells after deep profile control in low permeability fractured reservoirs
  58. Depiction and analysis of a modified theta shaped double negative metamaterial for satellite application
  59. An attempt to geometrize electromagnetism
  60. Structure of traveling wave solutions for some nonlinear models via modified mathematical method
  61. Thermo-convective instability in a rotating ferromagnetic fluid layer with temperature modulation
  62. Construction of new solitary wave solutions of generalized Zakharov-Kuznetsov-Benjamin-Bona-Mahony and simplified modified form of Camassa-Holm equations
  63. Effect of magnetic field and heat source on Upper-convected-maxwell fluid in a porous channel
  64. Physical cues of biomaterials guide stem cell fate of differentiation: The effect of elasticity of cell culture biomaterials
  65. Shooting method analysis in wire coating withdrawing from a bath of Oldroyd 8-constant fluid with temperature dependent viscosity
  66. Rank correlation between centrality metrics in complex networks: an empirical study
  67. Special Issue: The 18th International Symposium on Electromagnetic Fields in Mechatronics, Electrical and Electronic Engineering
  68. Modeling of electric and heat processes in spot resistance welding of cross-wire steel bars
  69. Dynamic characteristics of triaxial active control magnetic bearing with asymmetric structure
  70. Design optimization of an axial-field eddy-current magnetic coupling based on magneto-thermal analytical model
  71. Thermal constitutive matrix applied to asynchronous electrical machine using the cell method
  72. Temperature distribution around thin electroconductive layers created on composite textile substrates
  73. Model of the multipolar engine with decreased cogging torque by asymmetrical distribution of the magnets
  74. Analysis of spatial thermal field in a magnetic bearing
  75. Use of the mathematical model of the ignition system to analyze the spark discharge, including the destruction of spark plug electrodes
  76. Assessment of short/long term electric field strength measurements for a pilot district
  77. Simulation study and experimental results for detection and classification of the transient capacitor inrush current using discrete wavelet transform and artificial intelligence
  78. Magnetic transmission gear finite element simulation with iron pole hysteresis
  79. Pulsed excitation terahertz tomography – multiparametric approach
  80. Low and high frequency model of three phase transformer by frequency response analysis measurement
  81. Multivariable polynomial fitting of controlled single-phase nonlinear load of input current total harmonic distortion
  82. Optimal design of a for middle-low-speed maglev trains
  83. Eddy current modeling in linear and nonlinear multifilamentary composite materials
  84. The visual attention saliency map for movie retrospection
  85. AC/DC current ratio in a current superimposition variable flux reluctance machine
  86. Influence of material uncertainties on the RLC parameters of wound inductors modeled using the finite element method
  87. Cogging force reduction in linear tubular flux switching permanent-magnet machines
  88. Modeling hysteresis curves of La(FeCoSi)13 compound near the transition point with the GRUCAD model
  89. Electro-magneto-hydrodynamic lubrication
  90. 3-D Electromagnetic field analysis of wireless power transfer system using K computer
  91. Simplified simulation technique of rotating, induction heated, calender rolls for study of temperature field control
  92. Design, fabrication and testing of electroadhesive interdigital electrodes
  93. A method to reduce partial discharges in motor windings fed by PWM inverter
  94. Reluctance network lumped mechanical & thermal models for the modeling and predesign of concentrated flux synchronous machine
  95. Special Issue Applications of Nonlinear Dynamics
  96. Study on dynamic characteristics of silo-stock-foundation interaction system under seismic load
  97. Microblog topic evolution computing based on LDA algorithm
  98. Modeling the creep damage effect on the creep crack growth behavior of rotor steel
  99. Neighborhood condition for all fractional (g, f, n′, m)-critical deleted graphs
  100. Chinese open information extraction based on DBMCSS in the field of national information resources
  101. 10.1515/phys-2018-0079
  102. CPW-fed circularly-polarized antenna array with high front-to-back ratio and low-profile
  103. Intelligent Monitoring Network Construction based on the utilization of the Internet of things (IoT) in the Metallurgical Coking Process
  104. Temperature detection technology of power equipment based on Fiber Bragg Grating
  105. Research on a rotational speed control strategy of the mandrel in a rotary steering system
  106. Dynamic load balancing algorithm for large data flow in distributed complex networks
  107. Super-structured photonic crystal fiber Bragg grating biosensor image model based on sparse matrix
  108. Fractal-based techniques for physiological time series: An updated approach
  109. Analysis of the Imaging Characteristics of the KB and KBA X-ray Microscopes at Non-coaxial Grazing Incidence
  110. Application of modified culture Kalman filter in bearing fault diagnosis
  111. Exact solutions and conservation laws for the modified equal width-Burgers equation
  112. On topological properties of block shift and hierarchical hypercube networks
  113. Elastic properties and plane acoustic velocity of cubic Sr2CaMoO6 and Sr2CaWO6 from first-principles calculations
  114. A note on the transmission feasibility problem in networks
  115. Ontology learning algorithm using weak functions
  116. Diagnosis of the power frequency vacuum arc shape based on 2D-PIV
  117. Parametric simulation analysis and reliability of escalator truss
  118. A new algorithm for real economy benefit evaluation based on big data analysis
  119. Synergy analysis of agricultural economic cycle fluctuation based on ant colony algorithm
  120. Multi-level encryption algorithm for user-related information across social networks
  121. Multi-target tracking algorithm in intelligent transportation based on wireless sensor network
  122. Fast recognition method of moving video images based on BP neural networks
  123. Compressed sensing image restoration algorithm based on improved SURF operator
  124. Design of load optimal control algorithm for smart grid based on demand response in different scenarios
  125. Face recognition method based on GA-BP neural network algorithm
  126. Optimal path selection algorithm for mobile beacons in sensor network under non-dense distribution
  127. Localization and recognition algorithm for fuzzy anomaly data in big data networks
  128. Urban road traffic flow control under incidental congestion as a function of accident duration
  129. Optimization design of reconfiguration algorithm for high voltage power distribution network based on ant colony algorithm
  130. Feasibility simulation of aseismic structure design for long-span bridges
  131. Construction of renewable energy supply chain model based on LCA
  132. The tribological properties study of carbon fabric/ epoxy composites reinforced by nano-TiO2 and MWNTs
  133. A text-Image feature mapping algorithm based on transfer learning
  134. Fast recognition algorithm for static traffic sign information
  135. Topical Issue: Clean Energy: Materials, Processes and Energy Generation
  136. An investigation of the melting process of RT-35 filled circular thermal energy storage system
  137. Numerical analysis on the dynamic response of a plate-and-frame membrane humidifier for PEMFC vehicles under various operating conditions
  138. Energy converting layers for thin-film flexible photovoltaic structures
  139. Effect of convection heat transfer on thermal energy storage unit
Downloaded on 15.2.2026 from https://www.degruyterbrill.com/document/doi/10.1515/phys-2018-0016/html
Scroll to top button