Home Comparison and analyses of two thermal performance evaluation models for a public building
Article Open Access

Comparison and analyses of two thermal performance evaluation models for a public building

  • Xuemei Sun , Saihong Zhu , Hengxuan Zhu , Runze Duan and Jin Wang EMAIL logo
Published/Copyright: December 31, 2019

Abstract

Recently, investigations on building thermal inertia are mainly involved with the materials of the building envelope. Usually, other influencing factors are ignored, such as room ventilation, indoor heat storage, indoor cold source, indoor heat source and human behavior. In this paper, two models based on thermodynamics are given to evaluate building thermal performance. One is thermal mass model, and the other one is thermal reserve coefficient model. Based on thermal response testing data in a non-heating season, the thermal mass model was adopted to classify the envelope type, and the delay rules between the indoor temperature and the outdoor meteorological parameters are analyzed. In a heating season, the delay rules among the outdoor temperature, indoor temperature and supply water temperature are obtained by changing the supply water temperature. Thermal performance of the targeted building is evaluated with the thermal reserve coefficient model. For the same public building, two evaluation models tend to be consistent. These two evaluation models presented in this paper can be applied for the optimal design of buildings envelope.

1 Introduction

Recently, building industry scale has a rapid growth. Building industry investment accounts for around 30-40% of total number in global infrastructure. After industry and agriculture, building energy consumption became the third largest fossil energy consumer as mentioned in Ref. [1]. According to the statistics in Ref. [2], residential building energy consumption occupied the second place after industry energy consumption in China. Allouhi et al. [3] pointed out that most of building energy consumption was from heating, ventilation, and air conditioning. Therefore, it is necessary to use renewable energy technologies and optimal operation schemes of energy supply systems for a reduction of building energy consumption. It was pointed out that the directions for the building energy savings were to optimize the building structure design and to construct the low-energy consumption buildings [4]. In addition, nanofluids have also made important contributions to energy savings in industrial applications [5].

Non-energy saving buildings occupy a larger percentage of the total building area around the world. For these buildings, large loss of cold or heat energy is caused by thermal bridges and cracks during refrigerating or heating season. Optimal design of energy supply systems and the upgrade of building envelope becomes the hot topics of the present studies.

Gu et al. [6] adopted several prediction methods and models to accurately forecast the medium-term heat load. These results were very useful for optimal design and operation in energy systems. Gagliano et al. [7] analyzed dynamic thermal characteristics for a lager historical building. They found that the installation of the refrigeration power was significantly reduced when the maximum cold load was delayed around 8-12 hours. Results indicated that thermal inertia and inner natural ventilation can reduce the overheating phenomenon and enhance the indoor thermal comfort. Johra et al. [8] studied effects of various factors on building thermal inertia, including materials of exterior envelope and energy storage performance of indoor furniture. They found that the structure of the envelope is the main factor, and the energy storage of the furniture can increase the building time constant and the elasticity coefficient of energy supply by 42% and 21%, respectively. Stazi et al. [9] investigated influence of high-performance thermal insulation materials for the buildings in the Mediterranean region. They used a modified ventilation device to solve problems of poor indoor thermal comfort and higher refrigeration energy consumption for these measured buildings. By the improvement of the indoor ventilation, the uncomfortable level and refrigeration energy consumption decreased by 20% and 43%, respectively. Based on thermal characteristics of the hollow brick wall, Sala et al. [10] compared experimental results with simulation results from a finite element analysis method. They found that the two-dimensional heat transfer model with the non-uniform structure showed the similar results to those from one-dimensional heat transfer model with uniform material, and the errors between these two models can be analyzed quantitatively. Desogus et al. [11] compared two on-site testing methods of thermal resistance of a building, and they found that the measured errors were mainly caused by the heat flux meter and manual operation in the non-destructive testing method. Aguilar et al. [12] established a transient model for thermal bridge phenomenon by using equivalent thermal wall method, and they showed the topological structures of two different thermal Bridges. Without a thermal bridge phenomenon, the heat flux will be underestimated by 25%. Gu et al. [13] presented a hybrid control scheme in a heating system with distributed variable speed pumps. This optimal operation strategy had obvious advantage in saving electricity energy, which can greatly reduce the installed electricity power for energy supply systems. According to building thermal inertia and energy utilization efficiency, Aste et al. [14] used a parameter simulation method to calibrate structural parameters of an office building, including operating condition, initial calibration model, and climatic condition. Medjelekh et al. [15] studied effects of thermal and wet inertia for indoor comfort of stone houses in tropical areas. It was found that when the moisture absorption material of porous media was used in the part of envelop structure, the indoor temperature decreased by 1.5°C, and the refrigeration energy saving rate increased by 31.5%. Liu [16] used a dimensionless analysis method of dynamic temperature response to determine the sub-valueswhich affected the heat storage capacity of building. Liu [17] investigated the integrated thermal inertia of residential buildings in a cold region of China.

In summary, most of these studies about thermal inertia are based on simulation analysis and thermodynamic models. However, it is difficult to establish a complex thermodynamic model and to choose a reasonable simulation software. Therefore, this article proposed two simple and effective models for analysis of building thermal performance, i.e., thermal mass model and thermal reserve coefficient model. Thermal response testing data of a public building is analyzed by using two rapid evaluation models, which can be recommended to apply in many industries.

1.1 Research object

The targeted building is built in 2005, and it is located in Tianjin, China. It contains five floors with a total construction area of 24,000 m2. Figure 1 presents the exterior and interior structures of the building. A typical room of this building was selected as the research object. Length, width and the height of the room size was measured as follows: 13.3 m×9.1m×3.8 m, and ratio of window to wall is 0.36. Adjacent rooms have the same function and structure as the tested room, and influence of adjacent rooms on heat transfer is ignored. In order to weaken effects of human disturbance and indoor ventilation, the test is conducted with two periods: the first stage was from 0:00 am on Oct 1th to 23:50 pm on Oct 5th, and the second stage was from 15:00 pm on Dec 11th to 12:00 am on Dec 12th, 2018.

Figure 1 Targeted building and typical room
Figure 1

Targeted building and typical room

A gas boiler as the heat source was used for the heat supply system, and the heat source was indirectly connected with the targeted building by a water-water plate heat exchanger. The schematic of the energy supply system was shown in Figure 2.

Figure 2 Schematic of the energy supply system
Figure 2

Schematic of the energy supply system

Some devices of this experimental system are shown in Figure 3. The energy-saving control device in each thermal entrance of the targeted building is used for hydraulic control and temperature adjustment of return water. A wireless temperature monitoring device is installed in the test room as shown in Figure 3 (b), and the indoor temperature is measured every 10 minutes. For the targeted building, the indoor temperature will decrease to save the heat energy during the night. In order to avoid freezing, the room temperature is set with a low limit value, and the electric control valve is automatically adjusted according to the set point of the room temperature. Figure 3 (c) presents a weather station which measures and transmits information of outdoor temperature, wind speed and solar radiation every one minute. As shown in Figure 3 (d), the differential scanning calorimeter is used to measure the specific heat capacity of the outer wall materials. Table 1 shows the tested parameters and specifications of the measurement devices.

Figure 3 Photos of used devices
Figure 3

Photos of used devices

Table 1

Tested parameters and device specifications

Serial number Tested parameters Device name Measuring range Precision
1 Supply and return water temperature Temperature sensor (PT100) −50 ∼ 150°C ±0.1%
2 Indoor temperature Wireless temperature monitoring device 0 ∼ 50°C ±0.2 K
3 Outdoor temperature Weather station −30 ∼ 70°C ±0.2 K
4 Specific heat capacity Differential scanning calorimeter −180 ∼ 720°C ±0.01 K
5 Thermal conductive coefficient Thermal characteristic analyzer 0.2 ∼ 2.0 W/(m·K) ±5%

The outer wall of the test room is made up of composited materials, including internal plastering, concrete, hollow bricks, insulation material, external plastering and exterior wall paint. The thermophysical parameters of the room structure are shown in Table 2.

2 Results and discussion

Thermal mass model and thermal reserve coefficient model were used to analyze the thermal performance of the targeted building during a non-heating season and a heating season, respectively. In a non-heating season, the building thermal inertia was studied by analyzing delay rules between outdoor temperature and indoor temperature. In a heating season, the indoor temperature changes with increasing or decreasing the second supply water temperature.

Table 2

Thermophysical parameters of the test room structure

Envelope name Area (m2) Envelope materials Thickness (mm) Thermal conductive coefficient (W/(m·K) Specific heat capacity (J/(kg·K) Density (kg·m3) Heat transfer coefficient (W/(m2·K))
South outer wall 50.54 Outer wall paint 1.5 0.75 1120 1100 1.12
Outer wall plaster 5.0 0.90 1050 1900
Concrete and hollow bricks 370.0 1.70 920 1500
Insulation material 20.0 0.04 1480 35
Inter wall plaster 5.0 0.90 1050 1900
South outer window 18.14 Single-glass 8.0 1.40 750 2500 6.09

2.1 Thermal mass model

Indoor temperature is considered as the evaluation index for indoor thermal comfort, without regard to thermal radiation, humidity and indoor ventilation. The change rule of the indoor temperature can be described by the first law of thermodynamics as follows:

(1) M C p d t i d τ = Q 1 + Q 2 + + Q n

where M is the mass of the envelope, and CP is the constant-pressure specific heat. ti, τ and Q represent indoor temperature, time of temperature change and inner heat source, respectively.

If the indoor temperature keeps stable or rising steadily due to a heat flux caused by one of inner heat sources, influence of other heat sources can be ignored. Then, Eq. (1) can be described as:

(2) d t i d τ = U A M C p ( t i t o )

where U is heat transfer coefficient, and A is heat transfer area. to is outdoor temperature.

If K is defined as the building thermal mass, then the Eq. (2) is introduced as:

(3) K = U A M C p = 1 n j = 1 n U j A j M j C j

According to the results calculated by Eq. (3), building types are presented in Ref. [18]. The classification and building type are shown in Table 3. When delay time is between 1-3 hours, the building type can be classified as the light structure; as the delay time is more than 3 hours, the building type can be defined as the comfortable structure; when the delay time tends to be infinity, the building type can be considered as the heavy structure.

Table 3

Classification of building type

Serial number Thermal mass Attenuation Delay Building type
1 1 ≤ K−1 ≤ 10 Small 1 ∼ 3h Light
2 10 ≤ K−1 ≤ 35 Important >3h Comfortable
3 35 ≤ K−1 ≤ 100 Very effective +∞ Heavy

According to Table 2 and Eq. (3), the K−1 is calculated as 4905 seconds, i.e., 1.36 hours. Therefore, the measured building type is classified as the light structure.

In order to validate the classification result of the targeted building type, an on-site thermal response test was conducted from 0:00 am on Oct 1th to 23:50 pm on Oct 5th in 2018. Outdoor temperature, wind speed and solar radiation were measured per minute. As shown in Figure 4, the peak value of the outdoor temperature was around 26-29°C, which appeared between 14:50 pm and 15:20 pm every day. During the testing period, the minimum value of every day appears at 06:00 am, and the temperature changes from 12°C to 14°C. Similarly, the change rule of solar total radiation was obvious, and the radiation value appears from 06:00 to 18:00 every day. The maximum solar total radiation was at 12:00 every day, and the instantaneous peak value was around 900-1000 W/m2.

Figure 4 Curves of outdoor temperature and solar radiation
Figure 4

Curves of outdoor temperature and solar radiation

However, the change rule of the outdoor wind speed is inconspicuous. As shown in Figure 5, the maximum wind speed is nearly 9 m/s on Oct 1th, and the average daily wind speed is 4.1 m/s. From Oct 2th to Oct 5th, the variation trend of the wind speed is relatively steady, and the average value is about 2.7 m/s.

Figure 5 Outdoor wind speed
Figure 5

Outdoor wind speed

During the testing period, the change rules of solar radiation and outdoor temperature are similar. In order to analyze influence of the wind speed on the building thermal inertia, it is necessary to research the rule between the wind speed and the heat transfer coefficient of the outer wall surface.

Clarke model in Ref. [19] shows an empirical model between the outdoor wind speed and the heat transfer coefficient of the rough surface as follows:

(4) h w = 5.678 a + b w 0.304 c

where hw is heat transfer coefficient, and w is wind speed. a, b, and c are the experiment coefficients. These experiment constants are shown in Table 4.

Table 4

Experimental constants of Clarke model

Wind speed (m/s) a b c
0.00 ≤ w ≤ 4.88 1.09 0.23 1.00
4.88 ≤ w ≤ 30.48 0.00 0.53 0.78

Figure 6 shows the curves of the wind speed, the heat transfer coefficient of the outer wall surface, and integrated heat transfer coefficient of the outer wall. The heat transfer coefficient of the outer wall surface is direct ratio to the wind speed as shown in Figure 6.

Figure 6 Relationships between the wind speed and the heat transfer coefficient
Figure 6

Relationships between the wind speed and the heat transfer coefficient

When the wind speed increases from 4 to 5 m/s, the heat transfer coefficient of the outer wall surface has a step change from 23.37 to 38.61 W/(m2·K). Simultaneously, the integrated heat transfer coefficient of the outer wall increased from 2.89 to 3.18 W/(m2·K). As the wind speed exceeds 5 m/s, the integrated heat transfer coefficient is stable, and the final value is around 3.55 W/(m2·K). During the testing period, the range of the daily average wind speed is between 2.7 to 4.1 m/s, and the corresponding integrated heat transfer coefficient changes between 2.69 and 2.91 W/(m2·K). In this case, if the difference between indoor and outdoor temperatures is the same value, the fluctuation of the heat flow caused by the various wind speed is within 8.18%. In other words, influence of the wind speed for the wall integrated heat transfer coefficient can be ignored.

Figure 7 shows the delay and the attenuation rules between indoor temperature and outdoor temperatures.Measured data indicates that the peak value of the outdoor temperature appears between 14:50 and 15:20, and the maximum value changes from 26 to 29.3°C. In addition, the peak value of the indoor temperature appears between 16:20 and 16:50, and the maximum value changes from 23.4 to 23.9°C. The delay time caused by indoor and outdoor temperatures is around 1-1.5 hours. It can be seen from Figure 5, the wind speed on Oct 1th is obviously higher than those on other testing days. Although the fluctuation of the heat flow caused by the various wind speed is within 8.18%, the delay time between the outdoor temperature and indoor temperature is different during the testing time. According to the classification of the building type as shown in Table 3, the temperature attenuation is small, and the delay time is short. In conclusion, the building type can be considered as the light structure. The overall envelope performance of the building needs to be improved in order to reduce the heat transfer coefficient of the outer windows, which can enhance the indoor thermal comfort.

Figure 7 Delay rule between indoor and outdoor temperature
Figure 7

Delay rule between indoor and outdoor temperature

2.2 Thermal reserve coefficient model

In heating season, the indoor temperature fluctuates with the outdoor temperature and the heat supply. As shown in Ref. [20], when the outdoor temperature and the supply water temperature change simultaneously, the change rule of the indoor temperature can be introduced as follows:

(5) Z = T ln t i 0 t o β ( t i t o ) t i 1 t o β ( t i t o )

where Z is time of indoor temperature change from ti0 to ti1, and ti0 is steady indoor temperature before changing the supply water. ti1 is steady indoor temperature after changing the supply water, and to is random outdoor temperature. t i is designed indoor temperature, and t o is designed outdoor temperature. T is time constant, which represents required time as the indoor temperature changes from the initial value to the new steady value with the fastest rate. β is limited heating coefficient, which is defined as a ratio of minimum needed heat load to the designed heat load at the designed outdoor temperature. Limited heating coefficient β is described as:

(6) β = t i 1 t o / t i t o

In this paper, the designed indoor and outdoor temperature are 18°C and −7°C, respectively. At a random outdoor temperature, the limited heating coefficient can be described as:

(7) β o = β t i t o / t o t o

If the Eq. (7) is introduced into Eq. (5), the Eq. (5) can be transformed as follows:

(8) Z = T ln t i 0 t o β o ( t o t o ) t i 1 t o β o ( t o t o )

Figures 8 and 9 show curves of outdoor temperature and indoor temperature with the changed water supply temperature from 15:00 pm on Dec 11th to 12:00 pm on Dec 12th, 2018, respectively. The second supply water temperature is adjusted by the electric valve on the primary side, which changes the flow rate of the primary supply water to meet the required temperature.

Figure 8 Curve of hourly outdoor temperature
Figure 8

Curve of hourly outdoor temperature

Figure 9 Curves of supply water and indoor temperature
Figure 9

Curves of supply water and indoor temperature

The experimental process is shown as follows: the second supply water temperature is decreased from 60°C to 55°C during 22:00 to 22:10 on Dec 11th, 2018. Then, the indoor temperature dropped from 17.9°C to 16.6°C during 22:30 pm on Dec 11th to 00:10 am on Dec 12th. Due to the reduction of the outdoor temperature, the indoor temperature also shows a slightly descending trend. The low temperature operation mode is finished at 5:00 am on Dec 12th, and the second supply water temperature is simultaneously increases to 60°C. Finally, the room temperature raises slowly to around 17.6°C between 10:00 pm and 11:00 pm on Dec 12th, and its change trend is stable. With increasing and decreasing the second supply water temperature, the change ranges of the indoor temperature and the water supply temperature are 2°C and 5°C, respectively.

The decreasing and increasing processes of the indoor temperature are about 2 hours and 5 hours, respectively. It is found that the increasing process is significantly slower than the decreasing process. The monitoring data of different stages are shown in Table 5.

Table 5

Monitoring parameters of different stages

Serial number Time Change tendency of indoor temperature Average indoor temperature (°C) Average outdoor temperature (°C)
1 18:00-22:00 stable 17.73 −5.42
2 22:00-00:00 decreasing 17.35 −7.30
3 00:00-05:00 stable 16.33 −8.20
4 05:00-10:00 increasing 16.32 −8.91
5 10:00-12:00 stable 17.56 −2.64

Table 5 shows that the indoor temperature begins to drop at 22:00 pm on Dec 11th, and finally remained stable at 05:00 on Dec 12th. Some critical data during the testing process is analyzed as follows: the average outdoor temperature values are −7.30°C and −8.20°C during the decreasing stage and the stable stage, respectively. Therefore, the average outdoor temperature is −7.75°C through the two stages. The average indoor temperature before the water supply temperature decreased is 17.73°C. The steady average indoor temperature after the reduction of the water supply temperature is 16.33°C. The limited heating coefficient is 0.87, and the decreasing time of the indoor temperature is 2 hours. By introducing these above values into Eq. (8), the thermal reserve coefficient is calculated as 35 hours. The thermal reserve coefficient is related to the heat flux of the envelope and the heat storage capacity of the room. Generally, the recommended value of the thermal reserve coefficient is between 40 and 70 hours.

As the thermal reserve coefficient in this article is less than the standard value, it is suggested that the thermal performance of the tested building should be improved.

3 Conclusions

A thermal response test was conducted for a public building, and two thermal performance evaluation models were adopted to estimate the thermal performance of the tested building. Evaluation results of these two models show the validity and the accuracy of the used methods. In a non-heating season, influence of weather factors on building thermal inertia was analyzed. In a heating season, the change rule of the indoor temperature was studied by raising and lowering the second supply water temperature. With the same testing conditions, the thermal response experiments are conducted repeatedly. In a non-heating season, the experimental results show that the delay time between the indoor temperature and the outdoor temperature is 1.1-1.5 hours, which is close to 1.36 hours from the calculation from the thermal mass model. The building type is classified as the light structure according to the research results. In a heating season, according to the thermal reserve coefficient model, the thermal reserve coefficient of the tested building is 35 hours, which is less than the recommend 40-70 hours. It is concluded that the building structure has poor thermal performance and heat storage capacity, which is consistent with the results by adopting the thermal mass model.

The two evaluation models of thermal performance are recommended for the buildings thermal response tests. The results will always hold regardless of weather, geographical site or operating conditions. Especially, the thermal reserve coefficient model can be considered as the priority option due to its simple experimental method and clear physical meaning. Therefore, the proposed two models are useful to analyze power savings in an energy supply system for a given building.

Nomenclature

A

area (m2)

C

specific heat capacity (J/kg·K)

h

heat transfer coefficient (W/m2·K)

K

reciprocal number of thermal mass (1/s)

n

total number

Q

heat source (W)

T

time constant

t

temperature (°C)

U

integrated heat transfer coefficient (W/m2·K)

Z

thermal reserve coefficient

Greek symbols

β

limited heating coefficient

τ

time (s)

Subscripts

i

indoor

j

the jth order

o

outdoor

w

wind

References

[1] Chel A., Kaushik G., Renewable energy technologies for sustainable development of energy efficient building, J. Alexandria Engineering Journal., 2018, 57(2), 655-699.10.1016/j.aej.2017.02.027Search in Google Scholar

[2] Zhao X.L., Na L., Ma C.B., Residential energy consumption in urban China: A decomposition analysis, J. Energy Policy., 2012, 41, 644-653.10.1016/j.enpol.2011.11.027Search in Google Scholar

[3] Allouhi A., Fouih Y.E., Kousksou T., Jamil A., Zeraouli Y., Mourad Y., Energy consumption and efficiency in buildings: current status and future trends, J. Cleaner Production., 2015, 109, 118–30.10.1016/j.jclepro.2015.05.139Search in Google Scholar

[4] Zhang Y.P., Lin K.P., Zhang Q.L., Di H.F., Ideal thermophysical properties for free-cooling (or heating) buildings with constant thermal physical property material, J. Energy and Buildings., 2006, 38(10), 1164-1170.10.1016/j.enbuild.2006.01.008Search in Google Scholar

[5] Wang J., Li G.L., Zhu H.X., Luo J., Sundén B., Experimental investigation on convective heat transfer of ferrofluids inside a pipe under various magnet orientations , J. International Journal of Heat and Mass Transfer., 2019, 132, 407-419.10.1016/j.ijheatmasstransfer.2018.12.023Search in Google Scholar

[6] Gu J.H., Wang J., Qi C.Y., Min C.H., Sundén B., Medium-term heat load prediction for an existing residential building based on a wireless on-off control system, J. Energy., 2018, 152, 709-718.10.1016/j.energy.2018.03.179Search in Google Scholar

[7] Gagliano A., Patania F., Nocera F., Signorello C., Assessment of the dynamic thermal performance ofmassive buildings, J. Energy and Buildings., 2014, 72, 361-370.10.1016/j.enbuild.2013.12.060Search in Google Scholar

[8] Johra H., Heiselberg P., Dréau J.L., Influence of envelope, structural thermal mass and indoor content on the building heating energy flexibility, J., Energy and Buildings., 2019, 183, 325-339.10.1016/j.enbuild.2018.11.012Search in Google Scholar

[9] Stazi F., Bonfigli C., Tomassoni E., Di P., Costanzo M., Placido., The effect of high thermal insulation on high thermal mass: Is the dynamic behavior of traditional envelopes in Mediterranean climates still possible, J. Energy and Buildings., 2015, 88, 367-383.10.1016/j.enbuild.2014.11.056Search in Google Scholar

[10] Sala J.M., Urresti A., Martín K., Flores I., Apaolaza A., Static and dynamic thermal characterization of a hollow brick wall: Tests and numerical analysis, J. Energy and Buildings., 2008, 40(8), 1513-1520.10.1016/j.enbuild.2008.02.011Search in Google Scholar

[11] Desogus G., Mura Salvatore, Ricciu R., Comparing different approaches to in situ measurement of building components thermal resistance, J. Energy and Buildings, 2011, 43(10), 2613-2620.10.1016/j.enbuild.2011.05.025Search in Google Scholar

[12] Aguilar F., Solano J.P., Vicente P.G., Transient modeling of high-inertial thermal bridges in buildings using the equivalent thermal wall method, J. Applied Thermal Engineering, 2014, 67(1-2), 370-377.10.1016/j.applthermaleng.2014.03.058Search in Google Scholar

[13] Aste N., Leonforte F., Manfren M., Mazzon M., Thermal inertia and energy efficiency-Parametric simulation assessment on a calibrated case study, J. Applied Energy, 2015, 145, 111-123.10.1016/j.apenergy.2015.01.084Search in Google Scholar

[14] Medjelekh D., Ulmet L., Abdou S., Dubois F., A field study of thermal and hygric inertia and its effects on indoor thermal comfort: Characterization of travertine stone envelope, J. Building and Environment, 2016, 106, 57-77.10.1016/j.buildenv.2016.06.010Search in Google Scholar

[15] Gu J.H., Wang J., Qi C.Y., Yu X.J., Sundén B, Analysis of a hybrid control scheme in the district heating system with distributed variable speed pumps, J. Sustainable Cities and Society, 2019, 48.10.1016/j.scs.2019.101591Search in Google Scholar

[16] Liu X., The research on integrated thermal inertia of the lightweight building under the effect of multiple factors, D. Tianjin, Tianjin University, 2014.Search in Google Scholar

[17] Han Y., Research on integrated thermal inertia of residential buildings in cold region of China, D. Tianjin, Tianjin University, 2011.Search in Google Scholar

[18] Fernández J.L., Porta-Gándara M.A., Chargoy N, Rapid on-site evaluation of thermal comfort through heat capacity in buildings, J. Energy and Buildings, 2005, 37(12), 1205-1211.10.1016/j.enbuild.2004.09.003Search in Google Scholar

[19] Clarke J.A., Energy simulation in building design, D. University of Strathclyde, Glasgow, Scotland: Adam Hilger Ltd, 1985.Search in Google Scholar

[20] Zhan T.W., Zou P.H., Research on cooling process of heating rooms and intermittent (or limited) heating of heat networks, J. District Heating, 1995, 6, 13-19Search in Google Scholar

Received: 2019-10-31
Accepted: 2019-11-24
Published Online: 2019-12-31

© 2019 X. Sun et al., published by De Gruyter

This work is licensed under the Creative Commons Attribution 4.0 International License.

Articles in the same Issue

  1. Regular Articles
  2. Non-equilibrium Phase Transitions in 2D Small-World Networks: Competing Dynamics
  3. Harmonic waves solution in dual-phase-lag magneto-thermoelasticity
  4. Multiplicative topological indices of honeycomb derived networks
  5. Zagreb Polynomials and redefined Zagreb indices of nanostar dendrimers
  6. Solar concentrators manufacture and automation
  7. Idea of multi cohesive areas - foundation, current status and perspective
  8. Derivation method of numerous dynamics in the Special Theory of Relativity
  9. An application of Nwogu’s Boussinesq model to analyze the head-on collision process between hydroelastic solitary waves
  10. Competing Risks Model with Partially Step-Stress Accelerate Life Tests in Analyses Lifetime Chen Data under Type-II Censoring Scheme
  11. Group velocity mismatch at ultrashort electromagnetic pulse propagation in nonlinear metamaterials
  12. Investigating the impact of dissolved natural gas on the flow characteristics of multicomponent fluid in pipelines
  13. Analysis of impact load on tubing and shock absorption during perforating
  14. Energy characteristics of a nonlinear layer at resonant frequencies of wave scattering and generation
  15. Ion charge separation with new generation of nuclear emulsion films
  16. On the influence of water on fragmentation of the amino acid L-threonine
  17. Formulation of heat conduction and thermal conductivity of metals
  18. Displacement Reliability Analysis of Submerged Multi-body Structure’s Floating Body for Connection Gaps
  19. Deposits of iron oxides in the human globus pallidus
  20. Integrability, exact solutions and nonlinear dynamics of a nonisospectral integral-differential system
  21. Bounds for partition dimension of M-wheels
  22. Visual Analysis of Cylindrically Polarized Light Beams’ Focal Characteristics by Path Integral
  23. Analysis of repulsive central universal force field on solar and galactic dynamics
  24. Solitary Wave Solution of Nonlinear PDEs Arising in Mathematical Physics
  25. Understanding quantum mechanics: a review and synthesis in precise language
  26. Plane Wave Reflection in a Compressible Half Space with Initial Stress
  27. Evaluation of the realism of a full-color reflection H2 analog hologram recorded on ultra-fine-grain silver-halide material
  28. Graph cutting and its application to biological data
  29. Time fractional modified KdV-type equations: Lie symmetries, exact solutions and conservation laws
  30. Exact solutions of equal-width equation and its conservation laws
  31. MHD and Slip Effect on Two-immiscible Third Grade Fluid on Thin Film Flow over a Vertical Moving Belt
  32. Vibration Analysis of a Three-Layered FGM Cylindrical Shell Including the Effect Of Ring Support
  33. Hybrid censoring samples in assessment the lifetime performance index of Chen distributed products
  34. Study on the law of coal resistivity variation in the process of gas adsorption/desorption
  35. Mapping of Lineament Structures from Aeromagnetic and Landsat Data Over Ankpa Area of Lower Benue Trough, Nigeria
  36. Beta Generalized Exponentiated Frechet Distribution with Applications
  37. INS/gravity gradient aided navigation based on gravitation field particle filter
  38. Electrodynamics in Euclidean Space Time Geometries
  39. Dynamics and Wear Analysis of Hydraulic Turbines in Solid-liquid Two-phase Flow
  40. On Numerical Solution Of The Time Fractional Advection-Diffusion Equation Involving Atangana-Baleanu-Caputo Derivative
  41. New Complex Solutions to the Nonlinear Electrical Transmission Line Model
  42. The effects of quantum spectrum of 4 + n-dimensional water around a DNA on pure water in four dimensional universe
  43. Quantum Phase Estimation Algorithm for Finding Polynomial Roots
  44. Vibration Equation of Fractional Order Describing Viscoelasticity and Viscous Inertia
  45. The Errors Recognition and Compensation for the Numerical Control Machine Tools Based on Laser Testing Technology
  46. Evaluation and Decision Making of Organization Quality Specific Immunity Based on MGDM-IPLAO Method
  47. Key Frame Extraction of Multi-Resolution Remote Sensing Images Under Quality Constraint
  48. Influences of Contact Force towards Dressing Contiguous Sense of Linen Clothing
  49. Modeling and optimization of urban rail transit scheduling with adaptive fruit fly optimization algorithm
  50. The pseudo-limit problem existing in electromagnetic radiation transmission and its mathematical physics principle analysis
  51. Chaos synchronization of fractional–order discrete–time systems with different dimensions using two scaling matrices
  52. Stress Characteristics and Overload Failure Analysis of Cemented Sand and Gravel Dam in Naheng Reservoir
  53. A Big Data Analysis Method Based on Modified Collaborative Filtering Recommendation Algorithms
  54. Semi-supervised Classification Based Mixed Sampling for Imbalanced Data
  55. The Influence of Trading Volume, Market Trend, and Monetary Policy on Characteristics of the Chinese Stock Exchange: An Econophysics Perspective
  56. Estimation of sand water content using GPR combined time-frequency analysis in the Ordos Basin, China
  57. Special Issue Applications of Nonlinear Dynamics
  58. Discrete approximate iterative method for fuzzy investment portfolio based on transaction cost threshold constraint
  59. Multi-objective performance optimization of ORC cycle based on improved ant colony algorithm
  60. Information retrieval algorithm of industrial cluster based on vector space
  61. Parametric model updating with frequency and MAC combined objective function of port crane structure based on operational modal analysis
  62. Evacuation simulation of different flow ratios in low-density state
  63. A pointer location algorithm for computer visionbased automatic reading recognition of pointer gauges
  64. A cloud computing separation model based on information flow
  65. Optimizing model and algorithm for railway freight loading problem
  66. Denoising data acquisition algorithm for array pixelated CdZnTe nuclear detector
  67. Radiation effects of nuclear physics rays on hepatoma cells
  68. Special issue: XXVth Symposium on Electromagnetic Phenomena in Nonlinear Circuits (EPNC2018)
  69. A study on numerical integration methods for rendering atmospheric scattering phenomenon
  70. Wave propagation time optimization for geodesic distances calculation using the Heat Method
  71. Analysis of electricity generation efficiency in photovoltaic building systems made of HIT-IBC cells for multi-family residential buildings
  72. A structural quality evaluation model for three-dimensional simulations
  73. WiFi Electromagnetic Field Modelling for Indoor Localization
  74. Modeling Human Pupil Dilation to Decouple the Pupillary Light Reflex
  75. Principal Component Analysis based on data characteristics for dimensionality reduction of ECG recordings in arrhythmia classification
  76. Blinking Extraction in Eye gaze System for Stereoscopy Movies
  77. Optimization of screen-space directional occlusion algorithms
  78. Heuristic based real-time hybrid rendering with the use of rasterization and ray tracing method
  79. Review of muscle modelling methods from the point of view of motion biomechanics with particular emphasis on the shoulder
  80. The use of segmented-shifted grain-oriented sheets in magnetic circuits of small AC motors
  81. High Temperature Permanent Magnet Synchronous Machine Analysis of Thermal Field
  82. Inverse approach for concentrated winding surface permanent magnet synchronous machines noiseless design
  83. An enameled wire with a semi-conductive layer: A solution for a better distibution of the voltage stresses in motor windings
  84. High temperature machines: topologies and preliminary design
  85. Aging monitoring of electrical machines using winding high frequency equivalent circuits
  86. Design of inorganic coils for high temperature electrical machines
  87. A New Concept for Deeper Integration of Converters and Drives in Electrical Machines: Simulation and Experimental Investigations
  88. Special Issue on Energetic Materials and Processes
  89. Investigations into the mechanisms of electrohydrodynamic instability in free surface electrospinning
  90. Effect of Pressure Distribution on the Energy Dissipation of Lap Joints under Equal Pre-tension Force
  91. Research on microstructure and forming mechanism of TiC/1Cr12Ni3Mo2V composite based on laser solid forming
  92. Crystallization of Nano-TiO2 Films based on Glass Fiber Fabric Substrate and Its Impact on Catalytic Performance
  93. Effect of Adding Rare Earth Elements Er and Gd on the Corrosion Residual Strength of Magnesium Alloy
  94. Closed-die Forging Technology and Numerical Simulation of Aluminum Alloy Connecting Rod
  95. Numerical Simulation and Experimental Research on Material Parameters Solution and Shape Control of Sandwich Panels with Aluminum Honeycomb
  96. Research and Analysis of the Effect of Heat Treatment on Damping Properties of Ductile Iron
  97. Effect of austenitising heat treatment on microstructure and properties of a nitrogen bearing martensitic stainless steel
  98. Special Issue on Fundamental Physics of Thermal Transports and Energy Conversions
  99. Numerical simulation of welding distortions in large structures with a simplified engineering approach
  100. Investigation on the effect of electrode tip on formation of metal droplets and temperature profile in a vibrating electrode electroslag remelting process
  101. Effect of North Wall Materials on the Thermal Environment in Chinese Solar Greenhouse (Part A: Experimental Researches)
  102. Three-dimensional optimal design of a cooled turbine considering the coolant-requirement change
  103. Theoretical analysis of particle size re-distribution due to Ostwald ripening in the fuel cell catalyst layer
  104. Effect of phase change materials on heat dissipation of a multiple heat source system
  105. Wetting properties and performance of modified composite collectors in a membrane-based wet electrostatic precipitator
  106. Implementation of the Semi Empirical Kinetic Soot Model Within Chemistry Tabulation Framework for Efficient Emissions Predictions in Diesel Engines
  107. Comparison and analyses of two thermal performance evaluation models for a public building
  108. A Novel Evaluation Method For Particle Deposition Measurement
  109. Effect of the two-phase hybrid mode of effervescent atomizer on the atomization characteristics
  110. Erratum
  111. Integrability analysis of the partial differential equation describing the classical bond-pricing model of mathematical finance
  112. Erratum to: Energy converting layers for thin-film flexible photovoltaic structures
Downloaded on 9.9.2025 from https://www.degruyterbrill.com/document/doi/10.1515/phys-2019-0089/html
Scroll to top button