Modelling 132 kV Substation for Surge Arrester Studies
-
Mohd Zainal Abidin Ab Kadir
Insulation coordination models are an essential part of power system studies and are used to determine the performance of a transmission line or substation. This paper generalizes the guidelines and parameters to be used in modelling the substation and in performing the analysis on the prediction of the transformer damage. Modelling parameters and the substation layout design are based and adapted from 132/11 kV Simpang Renggam Ayer Hitam substation in Johor Baharu, Malaysia, courtesy of the Tenaga Nasional Berhad (TNB). The model is based on the single phase line model, as was suggested by the IEEE, to be adequate to represent the substation in transient analysis simulation. Extensive analyses on the placement of the surge arresters at the substation and a prediction of the transformer damage are also presented. The results obtained from this analysis are then compared with the suggested Basic Lightning Insulation Level (BIL) by the TNB, according to the standards, for assessing the percentage of transformer damage and optimizing the substation performance in terms of its reliability and cost effectiveness.
©2011 Walter de Gruyter GmbH & Co. KG, Berlin/Boston
Artikel in diesem Heft
- Article
- Star-Connected Autotransformer-Based Full-Wave AC-DC Converters
- A Probability Method for Very Short-Term Steady State Analysis of a Distribution System with Wind Farms
- Study on an Anti Power-Stealing Monitoring System for a Rural Power Grid in China
- Control Lyapunov Function for Series and Parallel Compensators with Energy Storage Capabilities
- L-Index Modulated Voltage Source Converter
- Modelling 132 kV Substation for Surge Arrester Studies
- Joint Market of Energy and Reserves Requirements considering Lost Opportunity Cost
Artikel in diesem Heft
- Article
- Star-Connected Autotransformer-Based Full-Wave AC-DC Converters
- A Probability Method for Very Short-Term Steady State Analysis of a Distribution System with Wind Farms
- Study on an Anti Power-Stealing Monitoring System for a Rural Power Grid in China
- Control Lyapunov Function for Series and Parallel Compensators with Energy Storage Capabilities
- L-Index Modulated Voltage Source Converter
- Modelling 132 kV Substation for Surge Arrester Studies
- Joint Market of Energy and Reserves Requirements considering Lost Opportunity Cost